Plan Review Notes
Plan Review Notes For Permit 98090666
Permit Number 98090666
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001.SHT PT3.3 & SHT P-D2 UNDER GROUND SANI
 TARY SEWER, DOES NOT MATCH SANITARY
 RISER DIAGRAM.
 SHT PD-2 STUDOR VENTS:SEC 905.7 SPC 94
 STUDOR VENTS ON HORIZONTAL BRANCHES OK.
 VENT STACKS TO RUN THRU ROOF EG.A4,A7,A6
 3.SHT P-D2 GEN. NOTES:(1)WE ARE ON 1994
 STD PLBG CODE. (6) DIELECTRIC UNIONS
 PROHIBITED, USE DIELECTRIC COUPLINGS OR
 NIPPLES. (15) PLUMBING FIXTURES: WATER
 CONSUPTION, TO COMPLY WITH TAB.406 SPC.