| Date |
Text |
| 2001-01-08 00:00:00 | 1-NEED LOAD CALCULATIONS ON THE FOLLOWIN | | | 4/0S, PP,LP,KP | | | 2-NEED FAULT CURRENT CALCULATION. | | | 3-OUTLET SPACING NOT TO LOCAL CODE. | | | 4-PANEL SCHEDULUE NOT COMPLETE. | | | 5-SEE PAGE E-1 FOR ELECTRICAL NOTES 12/8 |
|