| 2023-07-21 15:43:16 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23070868 |
| | 7/21/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) THE PERMIT APPLICATION INDICATES LIKE FOR LIKE GAS |
| | POOL HEATER REPLACEMENT HOWEVER I WAS UNABLE TO FIND A |
| | PERMIT RECORD FOR A POOL HEATER AT THE RESIDENCE. THE |
| | LAST GAS PLAN SUBMITTED WAS UNDER PERMIT 19070834 AND |
| | THE APPROVED RISER SHOWS PIPING TO A EXTERIOR TANKLESS |
| | WATER HEATER AND A GAS RANGE INSIDE THE HOUSE. PLEASE |
| | PROVIDE A COMPLETE GAS RISER DRAWING INCLUDES THE GAS |
| | PIPING TO THE POOL HEATER AND PIPING TO ALL EXISTING |
| | GAS PIPING AND APPLIANCES AT THE RESIDENCE- SECTION |
| | G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 |
| | FUEL GAS- THE RISER SHALL INDICATE: |
| | |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS AND OUTLET PRESSURES. |
| | F) PIPE SIZING TABLES. |
| | |
| | 2) PROVIDE A BASIC SITE PLANS SHOWING THE LOCATION OF |
| | THE POOL HEATER WITH EXHAUST PUTLET CLEARNCE |
| | MEASUREMENTS TO OPERABLE WINDOWS AND DOORS- SEC. 2427.8 |
| | FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |