2023-07-20 12:56:22FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 LIGHT OVER TUB CAN BE WITHIN 8' OF THE RIM OF THE TUB.
  
 410.10 (D) BATHTUB AND SHOWER AREAS.
  
 NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-,
 OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS,
 OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED
 WITHIN A ZONE MEASURED 900 MM (3 FT) HORIZONTALLY AND
 2.5 M (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM
 OR SHOWER STALL THRESHOLD. THIS ZONE IS ALL
 ENCOMPASSING AND INCLUDES THE SPACE DIRECTLY OVER THE
 TUB OR SHOWER STALL. LUMINAIRES LOCATED WITHIN THE
 ACTUAL OUTSIDE DIMENSION OF THE BATHTUB OR SHOWER TO A
 HEIGHT OF 2.5 M (8 FT) VERTICALLY FROM THE TOP OF THE
 BATHTUB RIM OR SHOWER THRESHOLD SHALL BE MARKED FOR
 DAMP LOCATIONS, OR MARKED FOR WET LOCATIONS WHERE
 SUBJECT TO SHOWER SPRAY.