| Plan Review Notes For Permit 23070491 |
| Permit Number |
23070491 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-20 16:22:40 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | CONDUCTORS TO TRANSFER SWITCH FROM METER CAN TO SMALL | | | YOU HAVE 350 AND YOU NEED 400 310.15(B)(7) | | | | | | PANEL "B" IS RATED AT 150 AND THE LOAD IS 185? 215.5 | | | | | | CONDUCTORS TO PANEL "B" TO SMALL 310.15(B)(7) |
|