2023-07-20 16:22:40FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CONDUCTORS TO TRANSFER SWITCH FROM METER CAN TO SMALL
 YOU HAVE 350 AND YOU NEED 400 310.15(B)(7)
  
 PANEL "B" IS RATED AT 150 AND THE LOAD IS 185? 215.5
  
 CONDUCTORS TO PANEL "B" TO SMALL 310.15(B)(7)