2023-07-20 17:04:42FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) STRUCTURE HAS MORE THAN 2 ELECTRICAL CIRCUITS GOING
 TO IT SO A PENEL WILL BE REQUIRED. IF YOU HAVE MORE
 THAN 6 CIRCUITS THEN A MAIN BREAKER WILL BE REQUIRE.
 225.30, 225.33
  
 225.30 NUMBER OF SUPPLIES.
  
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN 225.30(A)
 THROUGH (E). FOR THE PURPOSE OF THIS SECTION, A
 MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE
 CIRCUIT.
  
 WHERE A BRANCH CIRCUIT OR FEEDER ORIGINATES IN THESE
 ADDITIONAL BUILDINGS OR OTHER STRUCTURES, ONLY ONE
 FEEDER OR BRANCH CIRCUIT SHALL BE PERMITTED TO SUPPLY
 POWER BACK TO THE ORIGINAL BUILDING OR STRUCTURE,
 UNLESS PERMITTED IN 225.30(A) THROUGH (E).
  
 225.33 MAXIMUM NUMBER OF DISCONNECTS.
 (A) GENERAL.
  
 THE DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY
 225.30 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR
 SIX CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN
 A GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A
 SWITCHBOARD OR SWITCHGEAR. THERE SHALL BE NO MORE THAN
 SIX DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION.
  
 2) SEPARATRE GROUNDING ELECTRODE SYSTEM WILL BE
 REQUIRED AT THE SEPARATE STRUCTURE.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE.
  
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED.
  
  