| 2023-07-17 13:27:05 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 607.1.1/613.1 - SHOW A DETAIL THAT INCLUDED |
| | THE PIPING AT THE WATER HEATER THAT INCLUDES THE |
| | REQUIRED ASSE 1017 MIXING DEVICE TO SHOW COMPLIANCE |
| | WITH THIS SECTION FOR THE HOT WATER DELIVERY. THIS IS |
| | NOT THE SAME REQUIREMENT FOR PUBLIC HAND |
| | WASHING/TEMPERED WATER DELIVERY. |
| | |
| | 2. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND |
| | SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR |
| | PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE |
| | DEVICE SHOULD CONFORM TO ASSE 1070. |
| | |
| | 3. 2020 FPC 712.2 - IN THE SEWAGE EJECTOR DETAIL, ADD A |
| | CHECK VALVE AND FULL OPEN SHUT OFF IN THE DETAIL TO |
| | SHOW COMPLIANCE WITH THIS SECTION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |