2023-07-17 13:27:051ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1/613.1 - SHOW A DETAIL THAT INCLUDED
 THE PIPING AT THE WATER HEATER THAT INCLUDES THE
 REQUIRED ASSE 1017 MIXING DEVICE TO SHOW COMPLIANCE
 WITH THIS SECTION FOR THE HOT WATER DELIVERY. THIS IS
 NOT THE SAME REQUIREMENT FOR PUBLIC HAND
 WASHING/TEMPERED WATER DELIVERY.
  
 2. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND
 SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR
 PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE
 DEVICE SHOULD CONFORM TO ASSE 1070.
  
 3. 2020 FPC 712.2 - IN THE SEWAGE EJECTOR DETAIL, ADD A
 CHECK VALVE AND FULL OPEN SHUT OFF IN THE DETAIL TO
 SHOW COMPLIANCE WITH THIS SECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  