| Plan Review Notes For Permit 23070130 |
| Permit Number |
23070130 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-21 12:58:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A 4" LINE TO BE REPLACED. | | | | | | IS THIS 4' LINE A WATER LINE SUPPLYING A FIRE SPRINKLER | | | SYSTEM? | | | | | | PER NFPA 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS | | | | | | IF SO, PLEASE INDICATE SUCH AND PROVIDE EQUIPMENT SPEC | | | SHEETS AND INSTALL PER NFPA 24 AND PLEASE ENSURE | | | COMPLIANCE AND PROVIDE A NOTE OF ACKNOWLEDGMENT | | | | | | IF DOMESTIC WATER LINE OR A DRAIN LINE PLEASE INDCATE | | | IT AS SUCH. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|