| 2023-07-20 14:39:44 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED, PLEASE PROVIDE A RESPONSE SHEET |
| | WITH RESUBMITTALS FOR THE FOLLOWING ITEMS: |
| | |
| | 1.) FBC A 902.1, THE BAR HEIGHT HAS BEEN INCLUDED IN |
| | THE |
| | ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN. |
| | 34" MAX.). |
| | THE ISSUE IS THAT THE ACCESSIBLE LOCATION AT THE BAR |
| | NEEDS TO BE PERMANENT SO THE INDIVIDUAL REQUIRING THE |
| | ACCESSIBLE LOCATION WILL NOT HAVE TO ADJUST/PULL UP THE |
| | BAR FOR USAGE. |
| | |
| | |
| | |
| | 4.) NOTICE: PLAN SHEETS A-3, E-1, E-2, & E-3 NEED TO |
| | HAVE A THIRD PARTY VERIFIABLE DIGITAL SIGNATURE BY THE |
| | DESIGN PROFESSIONAL. PLEASE SEE THE SIGNATURE REVIEW |
| | COMMENTS. |
| | A.)DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND |
| | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A |
| | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND |
| | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A |
| | VALID DIGITAL SIGNATURE. |
| | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR |
| | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH |
| | 61G1-16 AND 61G15, F.A.C. |
| | B.)SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |