| Plan Review Notes For Permit 23070005 |
| Permit Number |
23070005 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-13 08:37:21 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23070005 | | | 7/12/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PERMIT APPLICATION INDICATES BACKFLOW #6 RPPA | | | FOR 2" WATER SERVICE, HOWEVER THE BF TABLE ON SHEET EX | | | 1 SITE PLAN INDICATES BACKFLOW #6 RPPA IS A ZURN MODEL | | | 350 ASTDA DDCA FOR FIRE LINE. PLEASE CORRECT ONE OR THE | | | OTHER- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|