| Date |
Text |
| 2023-07-06 14:17:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS OF NEW FLOORING ON ONE OF THE |
| | FLOOR PLANS HOWEVER, THERE IS NO SPEC SHEET NOR A |
| | PRODUCT NAME FOR THE ACTUAL PROPOSED FLOORING. |
| | |
| | FLOORING CAN HAVE DIFFERENT TYPES AND CAN BE |
| | MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE TESTED |
| | AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| | THE CLASSES SPECIFIED |
| | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| | CRITICAL RADIANT FLUX |
| | REQUIREMENTS. |
| | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.45 W/CM2, AS DETERMINED |
| | BY THE TEST DESCRIBED IN 10.2.7.3. |
| | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.22 W/CM2, BUT LESS |
| | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| | 10.2.7.3. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| | TYPE, PRODUCT NAME AND, IF APPLICABLE, THE PRODUCT SPEC |
| | SHEETS INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED, BUT NEEDS TO BE INDICATED ON THE |
| | PLAN. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | 2) THERE ARE INDICATION OR WLL & CEILIGN WORK |
| | THROUGHOUT THE UNIT. |
| | |
| | DO NOT PAINT OVER FIRE ALARM DEVICES/EQUIPMENT. |
| | |
| | THE FA SYSTEM SHALL BE MAINTAINED THROUGHOUT DEMO AND |
| | CONSTRUCTION. |
| | |
| | ANY WORK/DAMAGE ON THE FA SYSTEM SHALL BE |
| | CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP |
| | DRAWING BY FA CONTRACTORS. |
| | |
| | PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| | NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |