| 2023-07-10 15:32:27 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - THE CHANGES TO THE |
| | PLUMBING REQUIRE THE PLUMBING PERMIT TO BE REOPENED. |
| | HOWEVER, THE PLUMBING CONTRACTOR'S INSURANCE IS EXPIRED |
| | AND NEEDS RENEWED. EITHER RENEW THE COI WITH THE |
| | PERMITTING DESK OR CHANGE CONTRACTORS SO I AN REOPEN |
| | THE PLUMBING PERMIT AND ADD THE APPROPRIATE INSPECTIONS |
| | TO INSEPECT THE LAUNDRY DRAIN AND SINK DRAIN. THESE |
| | WERE NOT LOOKED AT DURING THE PLUMBING INSPECTION. |
| | |
| | 2. 2017 WPB AMENDS 107.2.1 - THE DRAWING DOES NOT |
| | ACCURATE DEPICT WHAT IS GOING INTO THE PROJECT. THE 3" |
| | FROM THE LAUNDRY EXITS IN THE OPPOSITE DIRECTION FROM |
| | THE LAUNDRY. ACCURATELY SHOW THE CONNECTIONS WITH WHAT |
| | IS ACTUALLY ON THE JOB. INCLUDE A FLOOR PLAN WITH THE |
| | PLUMBING PAGES TO SHOW THE ROUTING OF THE DRAINS IN |
| | REFERENCE TO THE LAYOUT AND FOOTPRINT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |