2023-07-12 08:31:21ELECTRIC REVIEW FAILED
  
 1) PLEASE CORRECT CONFLICTS WITH ELECTRICAL PLANS.
 RISER DETAILS TWO ELECTRIC PANELS AS 125 AMP, ONE
 EXISTING AND ONE NEW WITH MAIN CIRCUIT BREAKERS FED BY
 A METER MAIN WITH A 125 AMP AND 200 AMP MAIN BREAKERS.
 PANEL SCHEDULE INCLUDED IN SUBMITTAL DETAILS PANEL, A,
 NEW LOAD CENTER,150 AMP, MAIN LUG ONLY LOCATED IN A
 UTILITY ROOM WITH VARIOUS LOADS. ELECTRICAL SERVICE
 CALCULATION IS DETAILED AS PANEL B, LOCATED IN UTILITY
 ROOM WITH VARIOUS ELECTRIC LOADS. THERE ARE TOO MANY
 CONFLICTS FOR THIS REVIEWER TO DO ANY KIND OF REVIEW
 FOR THE ELECTRICAL SERVICE. PLEASE CORRECT AS
 APPLICABLE AND ENSURE TO INCLUDE ALL DETAILS CORRECTLY
 AND IN COMPLIANCE WITH ALL 2017 NEC CODE REQUIREMENTS.
 FBC 107.2
  
 2) PLEASE PROVIDE MORE DETAIL AS TO KITCHEN AREA.
 APPLIANCES IF ANY, SINKS, COUNTER AREAS ETC. FBC 107.2
  
 3) PROVIDE DETAILS THIS KITCHEN WILL BE PROVIDED WITH 2
 SMALL APPLIANCE 20 AMP CIRCUITS IN ACCORDANCE WITH NEC
 210.11 (C)(1)
  
 4) PLEASE DETAIL RECEPTACLE CIRCUIT AS 20 AMP IN
 ACCORDANCE WITH NEC 210.11)3)(C)
  
 5) PLEASE DETAIL THE CORRECTLY SPACED RECEPTACLES IN
 MAIN AREA IN ACCORDANCE WITH NEC 210.52
  
 6) PLEASE DETAIL AN OUTDOOR RECEPTACLES IN ACCORDANCE
 WITH NEC 210.52(E)(1)
  
 7) PLEASE DETAIL THE REQUIRED DIGITAL SIGNATURE FROM
 THE ENGINEER OF RECORD
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  