| Date |
Text |
| 2023-07-12 08:31:21 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLEASE CORRECT CONFLICTS WITH ELECTRICAL PLANS. |
| | RISER DETAILS TWO ELECTRIC PANELS AS 125 AMP, ONE |
| | EXISTING AND ONE NEW WITH MAIN CIRCUIT BREAKERS FED BY |
| | A METER MAIN WITH A 125 AMP AND 200 AMP MAIN BREAKERS. |
| | PANEL SCHEDULE INCLUDED IN SUBMITTAL DETAILS PANEL, A, |
| | NEW LOAD CENTER,150 AMP, MAIN LUG ONLY LOCATED IN A |
| | UTILITY ROOM WITH VARIOUS LOADS. ELECTRICAL SERVICE |
| | CALCULATION IS DETAILED AS PANEL B, LOCATED IN UTILITY |
| | ROOM WITH VARIOUS ELECTRIC LOADS. THERE ARE TOO MANY |
| | CONFLICTS FOR THIS REVIEWER TO DO ANY KIND OF REVIEW |
| | FOR THE ELECTRICAL SERVICE. PLEASE CORRECT AS |
| | APPLICABLE AND ENSURE TO INCLUDE ALL DETAILS CORRECTLY |
| | AND IN COMPLIANCE WITH ALL 2017 NEC CODE REQUIREMENTS. |
| | FBC 107.2 |
| | |
| | 2) PLEASE PROVIDE MORE DETAIL AS TO KITCHEN AREA. |
| | APPLIANCES IF ANY, SINKS, COUNTER AREAS ETC. FBC 107.2 |
| | |
| | 3) PROVIDE DETAILS THIS KITCHEN WILL BE PROVIDED WITH 2 |
| | SMALL APPLIANCE 20 AMP CIRCUITS IN ACCORDANCE WITH NEC |
| | 210.11 (C)(1) |
| | |
| | 4) PLEASE DETAIL RECEPTACLE CIRCUIT AS 20 AMP IN |
| | ACCORDANCE WITH NEC 210.11)3)(C) |
| | |
| | 5) PLEASE DETAIL THE CORRECTLY SPACED RECEPTACLES IN |
| | MAIN AREA IN ACCORDANCE WITH NEC 210.52 |
| | |
| | 6) PLEASE DETAIL AN OUTDOOR RECEPTACLES IN ACCORDANCE |
| | WITH NEC 210.52(E)(1) |
| | |
| | 7) PLEASE DETAIL THE REQUIRED DIGITAL SIGNATURE FROM |
| | THE ENGINEER OF RECORD |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |