| 2023-07-07 11:37:08 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE |
| | REPORT PREPARED BY A FLORIDA REGISTERED DESIGN |
| | PROFESSIONAL. |
| | 2. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH |
| | TESTING APPLICATION STANDARD TAS 105 AS REQUIRED BY |
| | LIMITATIONS #6 OF MIAMI-DADE COUNTY NOA NO.: |
| | 20-0721.08. |
| | 3. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| | CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER; TO CORRECT EXPOSURE |
| | CATEGORY, DESIGN PRESSURES & NAILING PATTERNS. THE |
| | CORRECT EXPOSURE CATEGORY FOR 618 CLEAR LAKE DR, WEST |
| | PALM BEACH, FL 33401 IS EXPOSURE CATEGORY D. INCLUDE |
| | THE SYSTEM TYPE & PAGE NUMBER OF NOA 20-0721.08. |
| | 4. SEC. 107.2.1.2 CITY AMENDMENTS. ROOF ZONES SPECIFIED |
| | ON THE CALCULATIONS SUBMITTED ARE INCORRECT. ARCHITECT |
| | NEEDS TO USE THE REVISED ZONES AND PROVIDE THE ZONES |
| | DIMENSIONS AS REQUIRED BY FIGURE R301.2(7) |
| | FBC-RESIDENTIAL OF CURRENT 2020 CODE. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN |
| | ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE |
| | DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |