| 2023-07-26 14:28:28 | ELECTRIC PLAN REVIEW FAILED |
| | |
| | 1) PLEASE PROVIDE A SEPARATE PERMIT FOR THE POOL, POOL |
| | BONDING AND ALL POOL RELATED EQUIPMENT. DETAIL ALL |
| | ITEMS ON A FLOOR PLAN THAT WILL BE REQUIRED TO BE |
| | BONDED IN ACCORDANCE WITH NEC 680.26. ALSO, DETAIL WITH |
| | THIS SEPARATE PERMIT ON A FLOOR PLAN INDICATING ALL |
| | LIGHTING, RECEPTACLES AND EQUIPMENT ARE INSTALLED IN |
| | ACCORDANCE WITH NEC 680.22. IN ADDITION, PROVIDE |
| | SPECIFICATIONS FOR POOL ONLY AS APPLICABLE TO THIS |
| | INSTALLATION. NO ALTERNATE OR GENERIC SPECIFICATIONS |
| | WILL BE ACCEPTABLE |
| | |
| | 2) PROVIDE DETAILS THAT ALL RECEPTACLES INSTALLED IN |
| | PATIENT TREATMENT AREAS ARE INSTALLED IN ACCORDANCE |
| | WITH NEC 517.13 |
| | |
| | 3) PROVIDE PANEL SCHEDULES WITH CLEAR LANGUAGE |
| | DETAILING THE BRANCH CIRCUITS SERVED FOR EACH |
| | OVERCURRENT DEVICE |
| | |
| | 4) PLEASE PROVIDE DETAILS IN POOL EQUIPMENT ROOM THAT |
| | INDICATE THE APPLICABLE WORKING CLEARANCES ARE PROVIDED |
| | FOR ALL ELECTRIC PANELS, DISCONNECTS IN ACCORDANCE WITH |
| | NEC 110.26 |
| | |
| | 5) PROVIDE A NOTE STATING ALL LOW VOLTAGE SYSTEMS |
| | INCLUDING BUT NOT LIMITED TO VOICE, DATA, FIRE ALARM, |
| | ACCESS CONTROL REQUIRE A SEPARATE PERMIT |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |