| Date |
Text |
| 2023-07-24 16:14:55 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23061432 |
| | 7/24/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS C-201 & P402: PLEASE SHOW THE LOCATION OF THE |
| | BACKFLOW PREVENTER FOR THE POTABLE WATER SERVICE- SEC. |
| | 608.1 FBC P, & SEC. C WPB UTILITIES CROSS CONNECTION |
| | MANUAL. PLEASE NOTE THE INSTALLATION SHALL BE DONE |
| | UNDER A SEPARATE PERMIT- SECS. 105.1 &107.2.1 WPB. |
| | |
| | 2) A1.0 & A1.3: PLEASE SHOW THE ACCESSIBLE ROUTE/PATH |
| | OF TRAVEL FROM BUILDING #3 TO BUILDING #1 RESTROOMS |
| | FROM THE MOST REMOTE POINT OF BUILDING #3 AND INCLUDE |
| | THE LENGTH OF THE ROUTE- SECS. 403.3.1 & 403.3.3 FBC P. |
| | |
| | 3) P303: SHOW KEYNOTE #206 IN THE KEYNOTES BOX- SEC. |
| | 107.2.1 WPB. |
| | |
| | 4) P303 & P603: SHOW THE PIPE RUNS FROM THE SUMP PUMPS |
| | TO THE RECOVERY TANK AND INCLUDE THE PIPE SIZES- SEC. |
| | 803.2 FBC P. |
| | |
| | 5) A1.2, P303: THE TANK IS LABELED RECIRC. ON A1.2 & |
| | RECOVERY TANK ON P303. PLEASE PROVIDE A BRIEF NARRATIVE |
| | TO CLARIFY THE FUNCTION OF THE TANK AND THE SYSTEM- |
| | SEC. 107.2.1 WPB. |
| | |
| | A) PROVIDE AN EQUIPMENT SCHEDULE FOR THE TANK LISTING |
| | MAKE AND MODEL AND CAPACITY. |
| | |
| | B) PLACE A NOTE TO INDICATE THE CHEMICALS IN THE TANK |
| | SHALL NOT BE DRAINED INTO THE SANITARY SEWER SYSTEM |
| | WITHOUT BEING THOROUGHLY DILUTED, NEUTRALIZED OR |
| | TREATED BY PASSING THROUGH AN APPROVED DILUTION OR |
| | NEUTRALIZING DEVICE- SEC. 803.1 FBC P. |
| | |
| | 6) P701: SHOW A CHECK VALVE AND FULL OPEN VALVE WILL BE |
| | INSTALLED ON THE DISCHARGE PIPES OF THE SUMP PUMPS- |
| | SEC. 712.2 FBC P. |
| | |
| | 7) P402, P603, & P801: PROVIDE THE MAKE AND MODEL OF |
| | THE EMERGENCY EYE WASH STATION; INDICATE IT CONFORMS TO |
| | ISEA Z358.1, AND IS EQUIPPED WITH AN ASSE 1071 MIXING |
| | VALVE FOR TEPID WATER DELIVERY BETWEEN 60-100 DEGREES |
| | F.- SECS. 411.1 & 411.3 FBC P. |
| | |
| | 8) A1.6 & P303 ROOF DRAINAGE: |
| | |
| | A) PROVIDE THE RAIN FALL RATE- SEC. 1106.1 FBC P. |
| | |
| | B) PROVIDE ROOF AREA AND GPM FLOW CALCULATIONS- 1106.2. |
| | |
| | C) PROVIDE THE GUTTER AND DOWNSPOUT SIZES- 1106.3 & |
| | 1106.6. |
| | |
| | D) SHOW DOWNSPOUT LOCATIONS- 1106.3. |
| | |
| | E) SHOW THE DRAINAGE DISPOSAL LOCATIONS- SEC. 1101.2. |
| | |
| | 9) CONCERNING THE BACKFLOW PREVENTER, A PERMIT |
| | APPLICATION SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING |
| | PLAN APPROVAL. YOU CAN SUBMIT AN APPLICATION TBD (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |