Plan Review Notes
Plan Review Notes For Permit 23061371
Permit Number 23061371
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-07-06 09:39:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO CLEAR INDICATION OF WHERE THE TWO (2)
 CLEAR EXIT PATHS ARE THAT LEAD TO A PUBLIC WAY ONCE A
 PERSON LEAVES THE OFFICE DOOR.
  
 IT IS UNDERSTOOD THAT THIS IS A CONSTRUCTION SITE,
 HOWEVER, ONCE OCCUPIED AND PER NFPA 101 AND 241, TWO (
 2) CLEAR AND PROTECTED EXIT PATHS ARE REQUIRED THAT
 LEAD TO A PUBLIC WAY.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THETHE TWO (2)
 EXIT PATHS AND DIMENSIONS TO A PUBLIC WAY.
  
  
 2) THERE ARE SEVERAL INDICATIONS OF STORAGE WITHIN THE
 PROVIDED FLOOR PLAN SHEETS.
  
 PLEASE IDENTIFY WHAT THIS STORAGE MATERIAL IS, HOW IT
 WILL BE STORED(PALLETS/PLASTIC WRAP. ETC) AND HOW HIGH.
  
 THESE AREAS MAY RESTRICT/IMPEDE THE PATH OF EXIT/EGRESS
 PER # 1 ABOVE IF INVLOVED IN FIRE.
  
 ADDITIONAL PROVIDE A STATEMENT IS THESE AREAS WILL BE
 INCLUDED WITH THE FIRE SPRINKLER PROTECTION?
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  