| 2023-07-03 06:15:02 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.3.5.1.5 - PLEASE SUBMIT THE GAS |
| | DOCUMENTS. INCLUDE: |
| | A) A SITE PLAN SHOWING THE LOCATION OF THE GENERATOR. |
| | INCLUDE DETAILS THAT WOULD INDICATE SETBACKS FROM |
| | PROPERTY LINES AND DISTANCES FROM STRUCTURE OPENINGS |
| | AND AIR INTAKES. |
| | B) PLEASE SUBMIT A GAS RISER DIAGRAM THAT INCLUDES ANY |
| | OF THE FOLLOWING APPLICABLE ITEMS. LOCATION OF |
| | SHUT-OFFS, THE PIPING MATERIAL, GAS PIPE SIZING METHOD |
| | AND BTU LOADS, VENTING OF APPLIANCES, COMBUSTION AIR |
| | CALCULATIONS, APPLIANCE SCHEDULE, THE TYPE OF GAS |
| | PROPOSED, METER LOCATION, AND THE EXISTING GAS SYSTEM |
| | (LABELING EXISTING AND NEW FOR CLARITY). |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |