| 2023-07-06 15:01:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SPEC SHEET STATES: |
| | |
| | INSTALLATION GUIDELINES |
| | |
| | 1) EXHAUST IS AIMED AWAY FROM OR PARALLEL TO THE |
| | STRUCTURE. |
| | |
| | 2) EXHAUST IS NOT DIRECTED AT PLAY AREAS, PATIOS OR |
| | OTHER AREAS WHERE PEOPLE CONGREGATE. |
| | |
| | 3) THE NEAREST WINDOW, VENT, DOOR OR SIMILAR STRUCTURE |
| | OPENING IS AT LEAST 5 FEET FROM THE EXHAUST END OF THE |
| | GENERATOR. |
| | |
| | 4) GENERATOR SET MUST BE INSTALLED A MINIMUM OF 18 |
| | INCHES FROM STRUCTURE PER NFPA 37, HOWEVER, ACTUAL |
| | DISTANCE MAY DIFFER BASED ON STATE AND LOCAL CODES. |
| | |
| | 5) WINDOWS & DOORS ON ADJACENT WALLS ARE CLOSED. |
| | |
| | 6) FURNACE AND OTHER SIMILAR INTAKES ARE AT LEAST 10 |
| | FEET FROM EXHAUST END OF GENERATOR. |
| | |
| | |
| | THE FLOOR PLAN DOES NOT INDICATE DETAILS IN COMPLIANCE |
| | WITH THE INSTALLATION GUIDELINES. |
| | |
| | PLEASE REVIEW AND PROVIDE THE APPLICABLE SPECIFIC |
| | DETAILS/DIMENSIONS. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF A NG LINE HOWEVER, THERE |
| | ARE NO DETAILS PER NFPA 54, INCLUDING SERVICE LINE |
| | LEENGTH, DEPTH OF COVERAGE, NEW GAS METER DIMENSION |
| | FROM AN ELECTICAL SPARK SOURCE, ETC. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE ALL |
| | APPLICABLE AND REQUIRED DIMENSIONS. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |