| Date |
Text |
| 2023-06-29 11:25:54 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 THE CITY OF WEST PALM BEACH IS NOT |
| | LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. PROVIDE |
| | A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| | USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. PLEASE |
| | NOTE THIS PROJECT IS LOCATED IN AN EXPOSURE C CATEGORY |
| | AREA. |
| | 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| | CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| | ROOFING TILE SYSTEM TO BE USED. INCLUDE COVER PAGE, |
| | EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING |
| | 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH OF EACH BUILDING WITH THE AREAS TO |
| | RECEIVE NEW ROOFING TILES CLEARLY IDENTIFIED ON |
| | DRAWING. PROVIDE TOTAL SQUARE FOOTAGE OF THE ROOF TILE |
| | AREA. PROVIDE TOTAL SQUARE FOOTAGE OF AREAS TO RECEIVE |
| | NEW ROOF TILES AND CLEARLY IDENTIFY ON ROOF SKETCH. NOT |
| | MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF |
| | SECTION OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE |
| | REPAIRED, REPLACED OR RECOVERED IN ANY 12-MONTH PERIOD |
| | UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION IS |
| | REPLACED TO CONFORM TO THIS CODE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |