Plan Review Notes For Permit 23061311
Permit Number 23061311
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-29 14:43:221ST REVIEW FBC-RES. 2020 PLUMBING
 PERMIT- 23061311
 6/29/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA RESIDENTIAL CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) POTABLE WATER SERVICE AND A SEWERAGE DISPOSAL SYSTEM
 ARE REQUIRED FOR THE JOB SITE TRAILER- SEC.108.2 WPB
 AND SEC. P2602.1 FBC RES. CURRENTLY NO MODULAR PLANS
 HAVE BEEN SUBMITTED HOWEVER IF THE TRAILER CONTAINS
 PLUMBING FIXTURES INTENDED FOR USE BY THE OCCUPANTS,
 PLEASE NOTE SEC. P2601 FBC RES BELOW-
 THE WATER-DISTRIBUTION AND DRAINAGE SYSTEM OF ANY
 BUILDING OR PREMISES WHERE PLUMBING FIXTURES ARE
 INSTALLED SHALL BE CONNECTED TO A PUBLIC WATER SUPPLY
 OR SEWER SYSTEM, RESPECTIVELY, IF AVAILABLE. WHERE
 EITHER A PUBLIC WATER-SUPPLY OR SEWER SYSTEM, OR BOTH,
 ARE NOT AVAILABLE, OR CONNECTION TO THEM IS NOT
 FEASIBLE, AN INDIVIDUAL WATER SUPPLY OR INDIVIDUAL
 (PRIVATE) SEWAGE-DISPOSAL SYSTEM, OR BOTH, SHALL BE
 PROVIDED. INDIVIDUAL WATER SUPPLIES SHALL BE
 CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE
 APPLICABLE STATE AND LOCAL LAWS. WHERE SUCH LAWS DO NOT
 ADDRESS ALL OF THE REQUIREMENTS SET FORTH IN NGWA-01,
 INDIVIDUAL WATER SUPPLIES SHALL COMPLY WITH NGWA-01 FOR
 THOSE REQUIREMENTS NOT ADDRESSED BY STATE AND LOCAL
 LAWS.
  
 2) WATER SERVICE SUBMITTAL: SHOW THE TYPE AND SIZE OF
 SERVICE LINE, SERVICE LINE RUN, POINT OF CONNECTION TO
 THE CITY MAIN, AND THE LOCATIONS OF THE WATER METER AND
 BACKFLOW PREVENTER. INDICATE THE TYPE AND SIZE OF
 BACKFLOW PREVENTER TO BE INSTALLED- SECS. P2901.1 &
 P2902.3 FBC RES AND SEC. E WPB UTILITIES CROSS
 CONNECTION MANUAL.
  
 A) CONCERNING THE BACKFLOW PREVENTER PLEASE NOTE A
 PERMIT APPLICATION SHALL BE SUBMITTED FOR THE
 INSTALLATION PRIOR TO APPROVAL OF THE PLUMBING PLAN
 REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 3) SANITARY SEWER SUBMITTAL: PROVIDE EITHER A DIRECT
 PIPE CONNECTION TO THE CITY SEWER LINE OR AN ONSITE
 SYSTEM SUCH AS A HOLDING TANK WITH PUMP-OUT CAPABILITY.
  
 A) SEWER CONNECTION- SHOW THE TYPE AND SIZE OF BUILDING
 DRAIN PIPE, THE DRAIN PIPE RUN, POINT OF CONNECTION TO
 THE SEWER LINE, AND CLEANOUT LOCATIONS- SEC. P3001.1
 FBC RES.
  
 B) PUMP TANK- SHOW THE LOCATION OF THE TANK ON THE
 PLAN, PROVIDE A PIPING DIAGRAM, AND SUBMIT
 MANUFACTURER???S SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  