| Plan Review Notes For Permit 23061309 |
| Permit Number |
23061309 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-12 15:39:03 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 SPECIFY THE SPECIFIC MOUNT TYPE, | | | FASTENER TYPE AND FASTENER SPACING FOR THE TOP AND | | | BOTTOM TRACKS AT EACH OF THE OPENINGS (1,2,3 & 4) THAT | | | WILL BE USED TO INSTALL THE ACCORDION SHUTTERS. YOU | | | HAVE CIRCLED MULTIPLE ITEMS ON THE PRODUCT APPROVAL, | | | BUT YOU DIDN'T SPECIFY WHICH OPENING THEY WILL BE USED | | | FOR. SUBMIT AN INSTALLATION SCHEDULE THAT LISTS EACH | | | OPENING AND PROVIDE THE REQUIRED INSTALLATION | | | INFORMATION FOR EACH. | | | | | | 2) SPECIFY THE SUBSTRATE (CONCRETE, WOOD, ETC.) THAT | | | YOU WILL BE ANCHORING TO AT THE TOP AND BOTTOM OF EACH | | | OPENING IN THE SCHEDULE. FBC 107.2.1 | | | | | | 3) THE ACTUAL MEAN ROOF HEIGHT OF THE BUILDING IS USED | | | TO DETERMINE THE DESIGN PRESSURES FOR ALL OF THE | | | OPENINGS. THE HEIGHT OF THE OPENING ITSELF IS NOT USED. | | | THE TABLE OFF DESIGN PRESSURES FOR COMPONENTS AND | | | CLADDING HAS A COLUMN FOR MEAN ROOF HEIGHT NOT OPENING | | | HEIGHT. FBC 1609 | | | |
|