Plan Review Notes
Plan Review Notes For Permit 23061287
Permit Number 23061287
Review Stop P
Sequence Number 1
Notes
Date Text
2023-07-18 10:13:001ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1/613.1 - SHOW DETAILS ON THE WATER
 HEATER DETAIL THAT COMPLIES WITH THIS SECTION. A MIXING
 VALVE IS REQUIRED AT THE WATER HEATER SO THAT THE
 THERMOSTAT ON THE WATER HEATER IS NOT THE LIMITING
 DEVICE FOR HOT WATER DELIVERY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  