| Plan Review Notes For Permit 23061217 |
| Permit Number |
23061217 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-19 09:10:28 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THE BOTTOM EXTENSION OF THE HANDRAIL IS HORIZONTAL AND | | | IT IS REQUIRED TO BE SLOPED TO COMPLY WITH FBC- | | | ACCESSIBILITY 505.10.3 BOTTOM EXTENSION AT STAIRS. AT | | | THE BOTTOM OF A STAIR FLIGHT, HANDRAILS SHALL EXTEND AT | | | THE SLOPE OF THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE | | | AT LEAST EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER | | | NOSING. EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE | | | LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL | | | OF AN ADJACENT STAIR FLIGHT. |
|