2023-07-07 09:13:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ NOT RESOLVED. THE SAME NOTES THAT WERE DENIED ARE
 ON THE SURVEY THAT WAS SUBMITTED.] THE GENERATOR
 EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET FROM ANY
 OPENINGS INTO A BUILDING. THIS CAN BE NOTED ON THE
 SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE
 OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 NOTE: IT APPEARS FROM THE SURVEY THAT THE GENERATOR IS
 4 FEET FROM THE WALL OF THE BUILDING. GENERATORS ARE
 TYPICALLY REQUIRED TO BE FIVE AWAY FROM A BUILDING FOR
 VENTILATION AND FIRE CONCERNS. CHECK THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GENERATOR. FBC FUEL GAS 616.1,
 NFPA 37 SECTION 4.1.4 AND UL2200
  