| Plan Review Notes For Permit 23061207 |
| Permit Number |
23061207 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-07 09:13:18 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [ NOT RESOLVED. THE SAME NOTES THAT WERE DENIED ARE | | | ON THE SURVEY THAT WAS SUBMITTED.] THE GENERATOR | | | EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET FROM ANY | | | OPENINGS INTO A BUILDING. THIS CAN BE NOTED ON THE | | | SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE | | | OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | NOTE: IT APPEARS FROM THE SURVEY THAT THE GENERATOR IS | | | 4 FEET FROM THE WALL OF THE BUILDING. GENERATORS ARE | | | TYPICALLY REQUIRED TO BE FIVE AWAY FROM A BUILDING FOR | | | VENTILATION AND FIRE CONCERNS. CHECK THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE GENERATOR. FBC FUEL GAS 616.1, | | | NFPA 37 SECTION 4.1.4 AND UL2200 | | | |
|