| 2023-07-26 13:26:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET 004 EXISTING - THERE IS AN INDICATION OF |
| | GENERAL QUESTIONS WITH EACH OF THE PICTURES. |
| | |
| | A LIFE SAFETY REVIEW FOR COMPLIANCE CAN NOT BE DONE |
| | WITH OPEN ENDED QUESTIONS WITH NO DETAILS. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE SPECIFIC |
| | DETAILS OF THE PROPOSED WORK IN SUPPORT OF THE CODE |
| | REQUIREMENTS FOR SUCH WORK. |
| | |
| | |
| | 2) SHEET A 141 & 142 - THERE IS AN INDICATION OF DRAFT |
| | ACROSS EACH OF THE ELEVATION DRAWINGS. |
| | |
| | A LIFE SAFETY REVIEW FOR COMPLIANCE CAN NOT BE DONE |
| | WITH A DRAFT DRAWING. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE SPECIFIC |
| | DETAILS OF THE PROPOSED WORK IN SUPPORT OF THE CODE |
| | REQUIREMENTS FOR SUCH WORK. |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF EXISTING FIRE SPRINLKER |
| | AND/OR FIRE ALARM SYSTEMS WITHIN THE EXISTING |
| | STRUCTURE. |
| | |
| | ANY FS & FA EXISTING SHALL BE EXTENDED TO THE ADDITION |
| | IF APPROVED. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW EXISTING BUILDING AND PROVIDE IF ANY FS & |
| | FA EQUIDPMENT DEVICES ARE PRESENT. |
| | |
| | IF SO, PROVIDE A NOTE OF ACKNOWLEDGMENT TO EXTEND FS & |
| | FA TO THE PROPOSED ADDITION UNDER SEPARATE PERMITS AND |
| | SHOP DRAWINGS. |
| | |
| | IF NOT, PROVIDE AN APPLICABLE NOTE INDICATING SUCH. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |