Plan Review Notes
Plan Review Notes For Permit 23061131
Permit Number 23061131
Review Stop E
Sequence Number 1
Notes
Date Text
2023-06-27 16:15:14FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN
 SIGHT FROM AND READILY ACCESSIBLE??? FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 2. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 3. THE PAGE WHERE THE LOAD CALCULATION AND ELECTRICAL
 SCOPE OF WORK ARE LOACTED IS NOT CLEAR AND CANNOT BE
 READ. PLEASE SUBMIT CLEAR, READABLE PLANS. FBC 107.2
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  