| 2023-07-03 15:33:25 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23061107 |
| | 7/3/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MP1.0: DRINKING FOUNTAINS ARE REQUIRED |
| | FIXTURES FOR MERCANTILE OCCUPANCIES AND A MINIMUM OF |
| | TWO ARE REQUIRED (ONE HI AND ONE LO)- SEE TABLE 403.1 |
| | AND SEC. 410.3 FBC P AND REVISE THE PLANS TO SHOW THE |
| | FIXTURE LOCATIONS AND THE PLUMBING PIPING DETAILS. |
| | |
| | 2) MP1.0: A MEANS OF LIMITING THE MAXIMUM ALLOWABLE HOT |
| | WATER DELIVERY TEMPERATURE OTHER THAN THE WATER HEATER |
| | THERMOSTAT IS REQUIRED- SEC. 607.1.1 FBC P. |
| | |
| | 3) MP1.0: TEMPERED WATER SHALL BE DELIVERED FROM THE |
| | LAVATORY- SECS. 419.5 & 607.1.2 FBC P. |
| | |
| | 4) MP1.0: THE 1/2--INCH HOT WATER FIXTURE SUPPLY PIPE |
| | TO THE LAVATORY IS EXCEEDING THE MAXIMUM ALLOWABLE 2 |
| | FT. DISTANCE FROM THE HOT WATER SOURCE- TABLE C404.5.1 |
| | FBC ENERGY. PROVIDE EITHER A POINT OF USE WATER HEATER |
| | OR A RECIRCULATION LINE AND PUMP. |
| | |
| | 5) A1.0: THE TOILET ROOM DOOR SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR THE LAVATORY- SEC. |
| | 603.2.3 FBC ACC. |
| | |
| | 6) A1.0: PLEASE PROVIDE DIMENSIONS OF THE WATER CLOSET |
| | AND LAVATORY CLEAR FLOOR SPACES- SECS. 604.3 & 606.2 |
| | FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |