Plan Review Notes
Plan Review Notes For Permit 23061107
Permit Number 23061107
Review Stop P
Sequence Number 1
Notes
Date Text
2023-07-03 15:33:251ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23061107
 7/3/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP1.0: DRINKING FOUNTAINS ARE REQUIRED
 FIXTURES FOR MERCANTILE OCCUPANCIES AND A MINIMUM OF
 TWO ARE REQUIRED (ONE HI AND ONE LO)- SEE TABLE 403.1
 AND SEC. 410.3 FBC P AND REVISE THE PLANS TO SHOW THE
 FIXTURE LOCATIONS AND THE PLUMBING PIPING DETAILS.
  
 2) MP1.0: A MEANS OF LIMITING THE MAXIMUM ALLOWABLE HOT
 WATER DELIVERY TEMPERATURE OTHER THAN THE WATER HEATER
 THERMOSTAT IS REQUIRED- SEC. 607.1.1 FBC P.
  
 3) MP1.0: TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORY- SECS. 419.5 & 607.1.2 FBC P.
  
 4) MP1.0: THE 1/2--INCH HOT WATER FIXTURE SUPPLY PIPE
 TO THE LAVATORY IS EXCEEDING THE MAXIMUM ALLOWABLE 2
 FT. DISTANCE FROM THE HOT WATER SOURCE- TABLE C404.5.1
 FBC ENERGY. PROVIDE EITHER A POINT OF USE WATER HEATER
 OR A RECIRCULATION LINE AND PUMP.
  
 5) A1.0: THE TOILET ROOM DOOR SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR THE LAVATORY- SEC.
 603.2.3 FBC ACC.
  
 6) A1.0: PLEASE PROVIDE DIMENSIONS OF THE WATER CLOSET
 AND LAVATORY CLEAR FLOOR SPACES- SECS. 604.3 & 606.2
 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  