| Notes |
| Date |
Text |
| 2023-07-27 18:16:27 | RESIDENTIAL(R3) SOLAR PANELS BUILDING AUDIT. | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23061098 | | | 901 42ND ST | | | | | | 1- THE ROOF PRESSURES SPECIFIED ON SHEET S-1 ARE TOO | | | LOW FOR A BUILDING LOCATED IN EXPOSURE C. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | NOTE: COORDINATE REVISED PRESSURES WITH CROSSRAIL | | | SYSTEM STRUCTURAL EVALUATION ON SHEETS S-11 AND S-12. | | | | | | 2- ROOF DIMENSION "A" NEEDS TO BE 4" NOT 3" AS REQUIRED | | | BY NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. REVISE | | | AS REQUIRED. | | | | | | 3- SHEET S-2 SHOWS A "TYPICAL SHINGLE ROOF LAYOUT". | | | ENGINEER OF RECORD NEEDS TO SHOW ROOF PLAN SHOWING | | | SPECIFIC LOCATION OF MODULES AND SPECIFIC ANCHORING | | | POINTS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY | | | AMENDMENTS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|