| 2023-07-19 08:23:07 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23061080 |
| | 7/18/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A-1 & P-2: PLEASE CLARIFY HOW THE NUMBER OF |
| | BOY'S AND GIRL'S BATHROOM FIXTURES WERE DETERMINED. |
| | REFER TO SEC. 468.3.5.1 FBC B AND TABLE 403.1 FBC P AND |
| | PROVIDE PLUMBING FIXTURE CALCULATIONS. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | NUMBER OF FIXTURES. FIXTURE RATIOS FOR EACH FIXTURE |
| | TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF EACH SEX. |
| | PLEASE NOTE, BY COMPARISON, THE PLAN SHOWS A GREATER |
| | NUMBER OF WATER CLOSETS/URINALS FOR BOYS THAN THE |
| | GIRLS. |
| | |
| | A) DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR E |
| | OCCUPANCIES- TABLE 403.1. WHERE ARE THESE FIXTURES |
| | LOCATED? |
| | |
| | B) REFER TO SEC. 604.1 EXCEPTION AND 604.9 AND INDICATE |
| | THE AGES OF THE STUDENTS WHO WILL BE USING THE BATHROOM |
| | FACILITIES. |
| | |
| | 2) A-1 & P-2: SEC. 213.1 STATES TOILET AND BATHING |
| | FACILITIES SHALL COMPLY WITH 213 INCLUDING 213.3 & |
| | 213.3.1. SEC. 213.3.1 STATES WHERE TOILET COMPARTMENTS |
| | ARE PROVIDED A MINIMUM OF ONE TOILET COMPARTMENT SHALL |
| | COMPLY WITH 604.8.1. PLEASE PROVIDE ONE WHEELCHAIR |
| | ACCESSIBLE COMPARTMENT IN EACH BATHROOM. |
| | |
| | A) IN ADDITION TO THE WHEELCHAIR ACCESSIBLE |
| | COMPARTMENT, AN AMBULATORY TOILET COMPARTMENT IS |
| | REQUIRED IN THE BOY'S BATHROOM- SEC. 213.3.1 FBC ACC. |
| | |
| | B) SHOW A CLEAR FLOOR SPACE DIAGRAM WITH DIMENSIONS AT |
| | THE LOCATION OF THE ACCESSIBLE URINAL- SEC.605.3. |
| | |
| | 3) A-1: DETAIL 4/A-1 SHOWS A 48X56-INCH CLEAR FLOOR |
| | SPACE FOR THE WATER CLOSET HOWEVER SEC. 604.3.1 FBC ACC |
| | REQUIRES A 60-INCH WIDE CLEAR FLOOR SPACE MEASURED |
| | PERPENDICULARLY FROM THE SIDE WALL. |
| | |
| | 4) A-1 MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS PER |
| | FBC ACC: |
| | |
| | A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | |
| | B) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SEC. 606.3. |
| | |
| | C) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3. |
| | |
| | D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES |
| | 604.5.1 & 604.5.2. |
| | |
| | E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC. |
| | 604.6. |
| | |
| | F) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | |
| | G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. |
| | |
| | H) HEIGHT OF THE ACCESSIBLE URINAL RIM ABOVE THE FINISH |
| | FLOOR, AND DEPTH OF THE URINAL FROM THE OUTER FACE TO |
| | THE BACK OF THE FIXTURE- SEC. 605.2. |
| | |
| | 5) P-1: ACCESSIBLE LAVATORY SINKS NOT INCLUDED IN THE |
| | FIXTURE SCHEDULE- SEC. 419.1 FBC P. |
| | |
| | 6) P-1 & P-2: REFER TO SEC. 468.3.5.6 FBC B AND PROVIDE |
| | A MINIMUM OF ONE FLOOR DRAIN AND ONE EASILY ACCESSIBLE |
| | HOSE BIB IN THE BOYS AND GIRLS BATHROOMS. |
| | |
| | 7) P-1 & P-2: REFER TO SEC. 468.3.5.12 AND PROVIDE |
| | MIXING VALVES AT THE LAVATORIES TO LIMIT THE HOT WATER |
| | DELIVERY TEMPERATURE TO 95 DEGREES F MINIMUM AND 110 |
| | DEGREES F MAXIMUM. |
| | |
| | 8) P1 & P2: PLEASE PROVIDE A PIPING DETAIL FOR THE NEW |
| | WATER HEATER SHOWING THE REQUIRED DEVICES AND PIPING |
| | CONNECTIONS- |
| | |
| | A) THERMOSTATIC MIXING VALVE- SEC. 607.1.1 FBC P. |
| | |
| | B) EXPANSION CONTROL DEVICE- SEC. 607.3. |
| | |
| | C) RELIEF VALVE, DRAIN PAN, PAN DRAIN LINE AND |
| | DISCHARGE LOCATION- SECS. 504.4- 504.7.2. |
| | |
| | 9) P2: THE LOCATION OF THE KEYED NOTED IN SCHEDULE ARE |
| | NOT SHOWN ON THE DRAWINGS DON'T APPEAR RELATIVE- SEC. |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |