Plan Review Notes
Plan Review Notes For Permit 23061059
Permit Number 23061059
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-28 09:21:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WOOD FLOOR ON THE
 APPLICATION, HOWEVER, THERE IS NO SPEC SHEET NOR A
 PRODUCT NAME FOR THE ACTUAL PROPOSED WOOD FLOORING.
  
 WOOD FLOORING CAN HACE DIFFERENT MEANINGS AND CAN BE
 MANUFACTURED AROUND THE WORLD BUT NOT ALL ARE TESTED
 AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING TYPE, PRODUCT NAME AND, IF APPLICABLE, THE
 PRODUCT SPEC SHEETS INDICATING THE FIRE BEHAVIOR
 RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, OR ACTUAL FULL
 HARDWOOD, PRODUCT SPEC SHEETS WOULD NOT BE REQUIRED,
 BUT NEEDS TO BE INDICATED ON THE PLAN.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved