| Plan Review Notes For Permit 23060976 |
| Permit Number |
23060976 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-07 14:04:24 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE HEIGHT OF THE AWNING FRAME AND FABRIC | | | ABOVE THE WALKWAY. FBC 3105.3.1.1 FABRIC AWNINGS AND | | | FABRIC-COVERED FRAMES LOCATED OVER PUBLIC PROPERTY OR | | | IN AREAS ACCESSIBLE TO THE GENERAL PUBLIC SHALL BE | | | CONSTRUCTED SO THAT NO RIGID PART OF SUCH FABRIC | | | AWNINGS OR FABRIC-COVERED FRAMES SHALL BE LESS THAN 7 | | | FEET 6 INCHES (2286 MM) FROM THE GRADE DIRECTLY BELOW, | | | AND NO PART OF THE CLOTH DROP SHALL BE LESS THAN 7 FEET | | | (2134 MM). | | | | | | 2) SUBMIT TWO SETS OF DETAILED AWNING REMOVAL | | | INSTRUCTIONS WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW | | | THIS IS DONE IN TERMS THAT A LAYMAN WILL UNDERSTAND. | | | THESE INSTRUCTIONS ARE TO BE PROVIDED TO THE PROPERTY | | | OWNER, OWNER'S REPRESENTATIVE OR LESSEE. FBC 107.2.1 | | | | | | 3) SUBMIT THE FLAME SPREAD CERTIFICATE FOR THE AWNING | | | FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR | | | FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION | | | PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD | | | INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE | | | WITH ASTM E84 OR UL 723. | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|