| 2023-07-06 09:19:19 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| | 20-0813.02 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE |
| | A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ROOF SKYLIGHT SYSTEM |
| | TO BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11602-R15 |
| | HAS BEEN REVISED TO FL11602-R16, IT COVERS MULTIPLE |
| | PRODUCTS & ATTACHMENT LIMITATIONS. SELECT PRODUCT & |
| | ATTACHMENT LIMITATION SYSTEM USED FOR NON-TILE |
| | APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. |
| | 3. SUBMITTED PRODUCT APPROVAL FL11727-R15 HAS BEEN |
| | REVISED TO FL11727-R16. PLEASE PROVIDE A COMPLETE SET, |
| | IT COVERS MULTIPLE INSTALLATION OPTIONS TO MEET DESIGN |
| | UPLIFT PRESSURES. PLEASE SELECT CORRECT FASTENER |
| | SPACING FROM TABLE ???A??? PAGE #5 OF THE EVALUATION |
| | REPORT THAT MEET OR EXCEED THE MINIMUM DESIGN PRESSURE |
| | REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C AREAS WITH A |
| | GABLE ROOF; ROOF SLOPES 2/12 MEAN ROOF HEIGHT UP TO 15 |
| | FT. (-121.00). ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |