| 2023-06-22 16:20:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS OF INSTALL NEW TILE THROUGHT |
| | THE UNIT, HOWEVER, THERE IS NO TILE PRODUCT TYPE NOR |
| | NAME OR MANUFACTURER'S SPECIFICATION SHEET. |
| | |
| | TILE CAN HAVE DIFFERENT MEANINGS AND NEEDS TO BE |
| | CLARIFIED FOR THE OFFICIAL RECORD. |
| | |
| | TILE FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE |
| | FLOORING TYPE, AND/OR PRODUCT NAME AND THE PRODUCT SPEC |
| | SHEETS INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF WORK IN THE BATHROOMS THAT |
| | MAY INVOLVE THE TENANT FIRE RATED SEPARATION WALLS. |
| | |
| | ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS ARE |
| | MAINTAINED & REPAIRED IF DAMAGED. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE |
| | PLAN SHEET. |
| | |
| | |
| | |
| | 3) THERE ARE INDICATIONS OF WORK INVLOVING THE CEILING |
| | AND INTERIOR WALL SURFACES. |
| | |
| | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE |
| | CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP |
| | DRAWING BY FS/FA CONTRACTORS. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE |
| | PLAN SHEET. |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |