| 2023-07-10 12:13:45 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23060831 | | | 7/10/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P-2 GAS RISER: PROVIDE A 1-INCH SCHEDULE 40 MAIN | | | PIPE AT THE METER AND A 1-INCH PE TO THE WATER HEATER | | | RISER- TABLES G2413.4(1) & G2413.4(7) FBC RES. | | | | | | 2) P-2: THE LOCATION OF THE TANKLESS WATER HEATER | | | EXHAUST OUTLET APPEARS TO BE WITHIN 4 FT. OF THE SHOWER | | | WINDOW- SEC. G2427.8 FBC RES. | | | | | | 3) P-2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | RANGE. PLEASE NOTE IF USING THE STANDARD INDOOR AIR | | | METHOD PER SEC. G2407.5.1 THE MINIMUM REQUIRED VOLUME | | | SHALL BE 50 CU. FT. PER 1000 BTUH. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|