2023-07-10 12:13:451ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23060831
 7/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-2 GAS RISER: PROVIDE A 1-INCH SCHEDULE 40 MAIN
 PIPE AT THE METER AND A 1-INCH PE TO THE WATER HEATER
 RISER- TABLES G2413.4(1) & G2413.4(7) FBC RES.
  
 2) P-2: THE LOCATION OF THE TANKLESS WATER HEATER
 EXHAUST OUTLET APPEARS TO BE WITHIN 4 FT. OF THE SHOWER
 WINDOW- SEC. G2427.8 FBC RES.
  
 3) P-2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE. PLEASE NOTE IF USING THE STANDARD INDOOR AIR
 METHOD PER SEC. G2407.5.1 THE MINIMUM REQUIRED VOLUME
 SHALL BE 50 CU. FT. PER 1000 BTUH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  