| Notes |
| Date |
Text |
| 2023-07-26 19:03:03 | ROOFING REVIEW: | | | | | | 1--PRODUCT APPROVALS | | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | | FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR | | | LATER AS A DEFERRED SUBMITTAL). | | | | | | (A) ROOFING UNDERLAYMENT SPECIFIED ON PLANS. | | | (B)BALCONY, ROOF DECK UNDERLAYMENT SPECIFIED ON PLANS | | | TO RECEIVE SPECIFIED FLOOR FINISH. | | | (C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | 2-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|