| 2023-07-26 18:50:03 | NFIP REVIEW: |
| | |
| | 1- THIS PROPERTY IS LOCATED IN AE FLOOD ZONE WITH A |
| | BASE FLOOD ELEVATION (BFE) OF 6 FEET BASED ON NAVD 88. |
| | THE PROPOSED SCOPE OF WORK IS CONSIDERED A SUBSTANTIAL |
| | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL |
| | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR |
| | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. CITY |
| | ORDINANCE 4729-17. |
| | |
| | REVISE FLOOR PLANS: |
| | A) ELEVATION CERTIFICATE SUBMITTED INDICATES AN |
| | EXISTING HOUSE WITH CRAWLSPACE AND FLOOD VENTS. CLARIFY |
| | WHY PLANS SUBMITTED DON'T SHOW ANY CRAWL SPACE AND |
| | FLOOD VENTS FOR THE EXISTING HOUSE. FLOOR PLANS NEED TO |
| | SHOW COMPLIANCE OF EXISTING HOUSE ENCLOSED AREA BELOW |
| | DESIGN FLOOD ELEVATION AS REQUIRED BY SEC. R322.2.2 |
| | FBC-RESIDENTIAL. PROVIDE COMPLETE INFORMATION SHOWING |
| | COMPLIANCE. SPECIFY FLOOD VENTS. SIZE, LOCATION, |
| | PRODUCT APPROVAL, ETC. |
| | NOTE: COORDINATE WITH ITEM #2 BELOW. |
| | |
| | B)REVISE FINISH FLOOR ELEVATION ON ALL PLANS, INCLUDING |
| | FOUNDATION PLAN. NEED TO USE NAVD 1988 ELEVATION DATUM |
| | NOT NGVD. ALSO, NEED TO SPECIFY THE OUTDOOR EQUIPMENT |
| | ELEVATION. REVISE ALL PLANS AND FLOOD MANAGEMENT |
| | INFORMATION ON SHEET G-1. SEC. 107.2.1 CITY AMENDMENTS. |
| | NOTE: COORDINATE WITH ITEM #2 BELOW. |
| | SPECIFY FINISH FLOOR ELEVATION ON ALL PLANS, INCLUDING |
| | FOUNDATION PLAN. |
| | |
| | 2- NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION |
| | CERTIFICATE AND SURVEY SHOWING ALL ELEVATIONS FOR |
| | VERIFICATION. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | NOTE: DURING THE CONSTRUCTION OF THIS STRUCTURE THREE |
| | DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE |
| | REQUIRED: |
| | (A)CONSTRUCTION DRAWINGS. |
| | (B)BUILDING UNDER CONSTRUCTION. |
| | (C)FINISHED CONSTRUCTION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |