| 2023-07-17 17:34:19 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23060804 | | | 5/17/23 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P0-02: THE ENERGYGAUGE REPORT LIST COMPLIANCE | | | DATA FOR GAS INSTANTANEOUS WATER HEATERS- 4 & 5, | | | HOWEVER THE WATER HEATERS SHOWN IN THE PLAN SCHEDULES | | | ARE ELECTRIC. PLEASE CORRECT THE CALCULATIONS OR THE | | | PLANS- SEC. 107.2.1 WPB. | | | | | | 2) A6-06: GRILLS ARE SHOWN ON THE ROOFTOP LOUNGE | | | HOWEVER NO INFORMATION ABOUT THE GRILLS HAVE BEEN | | | PROVIDED. PLEASE LABEL THE GRILLS AS EITHER GAS OR | | | ELECTRIC AND LIST THE MAKES AND MODELS ON THE PLAN- | | | SEC. 107.2.1 WPB. | | | | | | 3) PLEASE NOTE THE FOLLOWING GAS PLAN SUBMITTAL | | | REQUIREMENTS PER SEC. 107.35.1.5 WPB IF APPLICABLE TO | | | THE PROJECT. | | | | | | A) GAS PIPING LAYOUT PLANS AND RISER DRAWING- SEC. | | | 402.1 FBC FG. | | | | | | B) COMBUSTION AIR FOR INTERIOR APPLIANCES- SEC. 304.1 | | | FBC FG. | | | | | | C) VENTING- SEC. 503.1. FBC FG. | | | | | | D) EQUIPMENT SCHEDULES- SECS. 623..1 & 624.1 FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|