| 2023-07-17 12:20:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) LIFE SAFETY & ELECTRICAL SHEETS - THERE APPEARS TO |
| | BE DISCREPANCIES OF EXIT SIGNS MARKING THE TRAVEL PATHS |
| | LEADING TO AN EXIT. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN ACCORDANCE |
| | WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS 11 THROUGH |
| | 43. |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS. |
| | 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO |
| | POINT IN AN EXIT |
| | ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING |
| | DISTANCE OR 100 FT (30 M), |
| | WHICHEVER IS LESS, FROM THE NEAREST SIGN |
| | |
| | ENSURE EXIT TRAVEL PATHS IS MARKED WITH EXIT SIGNS PER |
| | NFPA 101 CH 7 ON BOTH THE LIFE SAFETY & ELECTRICAL |
| | PLANS. |
| | |
| | 2) FIRE ALARM DOCUMENTATION - THERE ARE INDICATIONS OF |
| | FIRE ALARM DEVICES/EQUIPMENT ON ELECTRICAL SHEET, |
| | HOWEVER, THERE DOES NOT APPEAR TO BE FIRE ALARM |
| | DOCUMENTATION IN COMPLIANCE WITH F.A.C. 61G |
| | |
| | PER F.A.C. |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER???S INTENDED USE AND |
| | PROPOSED PROTECTION OF THE BUILDING OR FACILITY AND TO |
| | PROVIDE SUFFICIENT DIRECTION TO THE INSTALLATION |
| | CONTRACTOR OR OTHER INTERESTED PARTIES REGARDING THE |
| | LAYOUT OF THE SYSTEM(S), SHALL BE INCLUDED IN THE FIRE |
| | PROTECTION SYSTEM ENGINEERING DOCUMENTS. |
| | |
| | |
| | 61G15-32.008 DESIGN OF FIRE ALARMS AND DETECTION |
| | SYSTEMS. |
| | (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE |
| | PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS, |
| | ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE |
| | SIGNALING OF EMERGENCY CONDITIONS. |
| | (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE |
| | FLORIDA BUILDING CODE (2007), THE FLORIDA FIRE |
| | PREVENTION CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY |
| | HAVING JURISDICTION. |
| | (3) FOR FIRE ALARM PLANS ON SMALL SYSTEMS BELOW THE |
| | THRESHOLD REQUIREMENTS FOR MANDATORY USE OF |
| | PROFESSIONAL ENGINEERING SERVICES, THE ENGINEER OF |
| | RECORD SHALL SPECIFY THE MINIMUM SYSTEM REQUIREMENTS. |
| | (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND |
| | DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS |
| | SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION |
| | WHEN APPLICABLE: |
| | (A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND, |
| | SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND |
| | NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. |
| | INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS |
| | DETERMINED BY THE SYSTEM???S SURVIVABILITY |
| | REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE |
| | PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS |
| | IT IS CLEAR FROM FEATURES SHOWN. |
| | (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND |
| | CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND |
| | SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS |
| | INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS, |
| | DAMPERS, AND DOORS. |
| | (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL |
| | NOTIFICATION DEVICES. |
| | (D) IDENTIFY THE CLASS AND STYLE OF CIRCUITS AS LISTED |
| | IN THE NFPA 72. |
| | (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND |
| | CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY |
| | SIGNALS BEING MONITORED OR ANNUNCIATED. |
| | (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR |
| | ADDRESSABLE, AND INDICATE ALL ZONING. |
| | (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED |
| | PROTECTIVE FEATURES. |
| | (H) LOCATE SYSTEM DEVICES THAT ARE SUBJECT TO |
| | ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR |
| | THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY |
| | OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR. |
| | (I) THE PLANS SHALL INCLUDE A SITE PLAN OF THE |
| | IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE |
| | OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE |
| | THE STRUCTURE. |
| | (J) IN BUILDINGS WERE SMOKE DETECTION WILL BE |
| | OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE |
| | ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND |
| | DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE |
| | OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A |
| | PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH |
| | AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (K) FIRE DETECTION SYSTEMS UTILIZING SMOKE DETECTION IN |
| | SITUATIONS WHERE SMOKE STRATIFICATION IS ANTICIPATED, |
| | THE DESIGN SHALL PROVIDE THE NECESSARY CRITERIA TO |
| | MITIGATE THE DETECTION PROBLEMS. |
| | (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA |
| | SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR |
| | STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING |
| | JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE |
| | FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING |
| | CODE (2007). |
| | (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO |
| | PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED |
| | EVACUATION FOR ALL HIGH-RISE BUILDINGS OR |
| | MULTI-TENANTED PROPERTIES AS DEFINED IN THE FLORIDA |
| | BUILDING CODE (2007). |
| | (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS, |
| | CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND |
| | BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE |
| | PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND |
| | INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED |
| | TO OPERATE THE SYSTEMS AS INTENDED OVER TIME. |
| | (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO |
| | SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED |
| | WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS) |
| | CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL |
| | BE COMPLETED USING THE EQUIPMENT MANUFACTURE???S DATA |
| | AND APPLICABLE NFPA 72 PROCEDURES. |
| | (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (7) WHEN THE ENGINEER DETERMINES THAT SPECIAL |
| | REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE |
| | UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE |
| | REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | |
| | EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR, |
| | THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G |
| | INFORMATION WITH THIS MASTER. |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTATION. |
| | |
| | |
| | 3) SHEET E 1-01 & FA 01A - THERE APPEARS TO BE |
| | INDICATIONS OF A FIRE PUMP, HOWEVER, THERE IS NO |
| | INDICATION OF THE FIRE PUMP EMERGENCY BACK-UP POWER NOR |
| | ITS FUEL SUPPLY. |
| | |
| | |
| | PER NFPA 101 CH 11 |
| | |
| | 11.8.5 EMERGENCY AND STANDBY POWER. |
| | 11.8.5.1 EMERGENCY POWER REQUIREMENTS FOR ELECTRIC FIRE |
| | PUMPS SHALL |
| | BE IN ACCORDANCE WITH NFPA 20. |
| | 11.8.5.2 EMERGENCY POWER REQUIREMENTS FOR DETECTION, |
| | ALARM, AND COMMUNICATIONS |
| | SYSTEMS SHALL BE IN ACCORDANCE WITH NFPA 72. |
| | 11.8.5.3 REQUIREMENTS FOR STANDBY POWER SHALL BE AS |
| | SPECIFIED IN |
| | 11.8.5.3.1 THROUGH 11.8.5.3. |
| | 11.8.5.3.1 TYPE 60, CLASS 1, LEVEL 1, STANDBY POWER IN |
| | ACCORDANCE WITH |
| | NFPA 110 SHALL BE PROVIDED. |
| | 11.8.5.3.2 THE STANDBY POWER SYSTEM SHALL HAVE A |
| | CAPACITY AND RATING |
| | SUFFICIENT TO SUPPLY ALL REQUIRED EQUIPMENT. |
| | 11.8.5.3.3 SELECTIVE LOAD PICKUP AND LOAD SHEDDING |
| | SHALL BE PERMITTED |
| | IN ACCORDANCE WITH NFPA 70. |
| | 11.8.5.3.4 THE STANDBY POWER SYSTEM SHALL BE CONNECTED |
| | TO THE |
| | FOLLOWING: |
| | (1) JOCKEY PUMP, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2 |
| | FOR SPECIAL PURPOSE |
| | INDUSTRIAL OCCUPANCIES |
| | (2) AIR COMPRESSOR SERVING DRY-PIPE AND PRE-ACTION |
| | SYSTEMS, EXCEPT |
| | AS OTHERWISE PROVIDED IN 40.4.2 FOR SPECIAL-PURPOSE |
| | INDUSTRIAL |
| | OCCUPANCIES |
| | (3) EMERGENCY COMMAND CENTER EQUIPMENT AND LIGHTING |
| | (4) NOT LESS THAN ONE ELEVATOR SERVING ALL FLOORS, WITH |
| | STANDBY POWER |
| | TRANSFERABLE TO ANY ELEVATOR |
| | (5) MECHANICAL EQUIPMENT FOR SMOKEPROOF ENCLOSURES |
| | (6) MECHANICAL EQUIPMENT REQUIRED TO CONFORM WITH THE |
| | REQUIREMENTS |
| | OF SECTION 9.3 |
| | (7) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PER NFPA |
| | |
| | NFPA 101 CHAPTER 7 SECTION 7.9 |
| | |
| | 7.9.1 FUEL TANKS SHALL BE SIZED TO ACCOMMODATE THE |
| | SPECIFIC |
| | |
| | EPS CLASS. |
| | |
| | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| | AND MAINTAINED |
| | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| | 54, NATIONAL |
| | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| | CODE. |
| | |
| | |
| | PLEASE PROVIDE DETAILS AND CONFIRMATION OF THE |
| | REQUIREMENTS. |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF COMPLIANCE WITH THE |
| | REQUIREMENTS OF EMERGENCY RADIO COMMUNICATIONS |
| | |
| | TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| | SYSTEMS. |
| | 24.9.1 GENERAL. |
| | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| | CAPABLE |
| | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| | FREQUENCIES |
| | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| | INSTALLED |
| | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| | AUTHORITY |
| | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| | DEGRADE |
| | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED |
| | FOR |
| | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| | SUCCESSFUL |
| | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| | FOR THE |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| | BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH |
| | FIRE DEPARTMENT. |
| | |
| | TESTING SHALL BE BY AN ACCEPTABLE NATIONAL STANDARD |
| | DOCUMENTING PERCENTAGES NOTED ABOVE AND BY ACTUAL RADIO |
| | TESTING BY FIRE PERSONNEL. |
| | |
| | IF THE MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL |
| | AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM |
| | 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | CONTACT SHALL BE MADE TO KEN DECKER, PALM BEACH COUNTY |
| | PUBLIC SAFETY RADIO SYSTEMS MANAGER, |
| | [email protected], 561-233-0837; AS OUR RADIOS OPERATE |
| | ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | NO PERMIT SHALL BE SUBMITTED OR BDA SYSTEM INSTALLED |
| | UNTIL ALL DOCUMENTATION IS REVIEWED BY PBC & THE OFFICE |
| | OF THE FIRE MARSHAL AND SUBSEQUENTLY APPROVED FOR |
| | INSTALL OR PARTIAL INSTALL. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE |
| | ON THE LIFE SAFETY PLAN SHEETS. |
| | |
| | |
| | |
| | 5) SHEET LS1-01 & STRUCTURAL SHEETS - THERE IS AN |
| | INDICATION OF A DOUBLE DOOR WITH DOOR OPENING OUT IN |
| | THE DIRECTION OF EGRESS, HOWEVER, THERE APPEARS TO BE A |
| | GATE/DOOR THAT OPENS IN AGAINST THE DIRECTION OF |
| | EGRESS. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPANCIES, |
| | AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 5A) IN ADDITION TO THE ABOVE, THE EGRESS CAPACITY WIDTH |
| | OF THE GATE/DOOR IS REDCUED FROM THE DOULBLE DOOR AND |
| | MAY NOT PROVIDE SUFFICIENT EXIT WIDTH FOR THE OCCUPANY |
| | LOAD. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.2.1.2.2* MEASUREMENT OF EGRESS CAPACITY WIDTH. |
| | |
| | 7.2.1.2.2.1 SWINGING DOOR ASSEMBLIES. FOR SWINGING DOOR |
| | ASSEMBLIES, |
| | EGRESS CAPACITY WIDTH SHALL BE MEASURED AS FOLLOWS: |
| | (1) THE MEASUREMENT SHALL BE TAKEN AT THE NARROWEST |
| | POINT IN THE DOOR |
| | OPENING. |
| | (2) THE MEASUREMENT SHALL BE TAKEN BETWEEN THE FACE OF |
| | THE DOOR LEAF |
| | AND THE STOP OF THE FRAME |
| | (3) FOR NEW SWINGING DOORS ASSEMBLIES, THE MEASUREMENT |
| | SHALL BE |
| | TAKEN WITH THE DOOR LEAF OPEN 90 DEGREES. |
| | (4) FOR ANY EXISTING DOOR ASSEMBLY, THE MEASUREMENT |
| | SHALL BE TAKEN |
| | WITH THE DOOR LEAF IN THE FULLY OPEN POSITION. |
| | (5) PROJECTIONS NOT MORE THAN 31???2 IN. (90 MM) AT |
| | EACH SIDE OF THE DOOR |
| | OPENINGS AT A HEIGHT OF NOT MORE THAN 38 IN. (965 MM) |
| | SHALL NOT BE |
| | CONSIDERED REDUCTIONS IN EGRESS CAPACITY WIDTH. |
| | (6) PROJECTIONS EXCEEDING 6 FT 8 IN. (2030 MM) ABOVE |
| | THE FLOOR SHALL |
| | NOT BE CONSIDERED REDUCTIONS IN EGRESS CAPACITY WIDTH. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE |
| | SPECIFIC DETAILS. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |