| 2023-07-18 16:41:18 | NEW 8 STORY R2 |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A1-05B - DOORS OPENING INTO THE CORRIDOR - |
| | PLEASE SHOW THAT THE DOORS COMPLY WITH FBC 1005.7.1 |
| | DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | |
| | 2) PLEASE SHOW THE STAIR RISER HEIGHTS TO COMPLY WITH |
| | FBC 1011.5.2 RISER HEIGHT AND TREAD DEPTH. |
| | STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM |
| | AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL |
| | BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT |
| | TREADS. |
| | |
| | 3) DRAWING S0-02 - WIND DESIGN DATA SHOWN SHOWS WIND |
| | SPEED AT 169MPH - SHOULD BE 170MPH PER FBC WPB SECTION |
| | 120 |
| | |
| | 4) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE GROUND |
| | FLOOR GARAGE TO THE INTERIOR OF THE BUILDING (CORRIDOR, |
| | LOBBY, RETAIL - ETC.) FBC FHA REQUIREMENT 1 - (FBC A |
| | 206.2.1) |
| | |
| | 5) PLEASE SHOW THE UNIT BATHROOM WALLS ON THE FLOOR |
| | PLANS THAT ARE TO HAVE GRAB BAR BACKING - FBC WPB |
| | REQUIREMENT 6 |
| | |
| | 6) 8TH FLOOR CLUB ROOM - PLEASE SHOW THE ACCESSIBLE |
| | SEATING, BAR COUNTER HEIGHT, KNEE AND TOE CLEARANCE - |
| | FBC WPB REQUIREMENT 2 |
| | |
| | 7) GROUND FLOOR RESTAURANT - PLEASE SHOW THE ACCESSIBLE |
| | SEATING (INCLUDING THE BAR AREA - COUNTER HEIGHT, KNEE |
| | AND TOE CLEARANCE ETC.) FBC A 226 |
| | |
| | 8) JOB COST PER ICC VALUATION TABLE ADDS UP TO A JOB |
| | COST OF $52,504,636.00 - PLEASE REVISE THE BUILDING |
| | PERMIT APPLICATION OR PROVIDE A COST BREAK DOWN TO |
| | SUPPORT THE JOB COST SHOWN ON THE PROVIDED BUILDING |
| | PERMIT APPLICATION. |
| | |
| | 9) THRESHOLD BUILDING INSPECTION FORMS - PLEASE READ |
| | AND FILL OUT THE REQUIRED DOCUMENTS AND PROVIDE COPIES |
| | OF THE LICENSES PER THE "GUIDELINES AND POLICIES FOR |
| | PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND |
| | RESIDENT INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A |
| | COPY. |
| | |
| | 10) FOR THE UNIT FLOORING ASSEMBLIES - THE FOLLOWING |
| | ACUSTICAL TEST REPORTS ARE REQUIRED: ( FLOORING TEST |
| | REPORTS CAN BE ADDED TO THE DEFERRED SUBMITTALS LIST) |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | |