| Plan Review Notes For Permit 23060795 |
| Permit Number |
23060795 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-26 14:44:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A FLOOR PLAN, HOWEVER, | | | THERE IS NO INDICATION OF WHAT IS EXISTING AND WHAT IS | | | PROPOSED. | | | | | | PER NFPA 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS | | | | | | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO | | | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE | | | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE MORE DETAIL IN | | | WHAT IS EXISTING AND WHAT IS PROPOSED. | | | | | | | | | 1A) THERE ARE INDICATIONS OF DOORS; ENTRANCE, 2 | | | SLIDING/POCKET, EMERGENCY DOOR, HOWEVER, THERE ARE NO | | | INDICATIONS OF OF DOOR HARDWARE/LOCKS/LATCHES. | | | | | | DOOR HARDWARE IN THE PATH OF EXITS SHALL COMPLY WITH | | | THE REQUIREMENTS OF NFPA 101 CH 7, MEANS OF EGRESS. | | | | | | PLEASE PROVIDE DOOR HARDWARE DETAILS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|