Plan Review Notes
Plan Review Notes For Permit 23060788
Permit Number 23060788
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-23 11:25:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF A NEW EXPANSIVE CANOPY OVER
 AN ASSEMBLY OCCUPANCY WITH EXISTING FIRE SPRINKLER
 PROTECTION, WITHIN THE EXISTING ASSEMBLY OCCUPANCY.
  
 THERE IS AN INDICATION A FLAME CERT WHICH IS REQQUIRED,
 HOWEVER, THERE NO INDICATION OF INSTALLING FIRE
 SPRINKLER PROTECTION UNDER THIS NEW CANOPY. AN
 INDICATION OF THE SPEC SHEET FOR THE FLOOR
 UNDERLAYMENT,
  
 PER NFPA 101, CH 12, 42 AND NFPA 13, FIRE SPRINKLER
 PROTECTION IS REQUIRED.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A NOTE OF
 ACKNOWLEDGMENT TO PROVIDE FIRE SPRINKLER PROTECTION
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  