| Plan Review Notes For Permit 23060788 |
| Permit Number |
23060788 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-23 11:25:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF A NEW EXPANSIVE CANOPY OVER | | | AN ASSEMBLY OCCUPANCY WITH EXISTING FIRE SPRINKLER | | | PROTECTION, WITHIN THE EXISTING ASSEMBLY OCCUPANCY. | | | | | | THERE IS AN INDICATION A FLAME CERT WHICH IS REQQUIRED, | | | HOWEVER, THERE NO INDICATION OF INSTALLING FIRE | | | SPRINKLER PROTECTION UNDER THIS NEW CANOPY. AN | | | INDICATION OF THE SPEC SHEET FOR THE FLOOR | | | UNDERLAYMENT, | | | | | | PER NFPA 101, CH 12, 42 AND NFPA 13, FIRE SPRINKLER | | | PROTECTION IS REQUIRED. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A NOTE OF | | | ACKNOWLEDGMENT TO PROVIDE FIRE SPRINKLER PROTECTION | | | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|