| 2023-06-20 14:09:52 | ELECTRICAL REVIEW FAILED |
| | 1) COVER SHEET DETAILS PATIO ENCLOSURE AS HABITABLE AND |
| | NON-HABITABLE. PLEASE EXPLAIN HOW THIS ROOM CAN BE |
| | BOTH. FBC 107.2 |
| | 2) ELECTRICAL RECEPTACLE SPACING DOES NOT APPEAR TO BE |
| | COMPLIANT WITH NEC 210.52. PLEASE CORRECT AS APPLICABLE |
| | 3) PLEASE PROVIDE REFERENCE TO KEYED NOTES ON SHEET S2. |
| | PLAN DOES NOT DETAIL IF THERE ARE OPERABLE DOORS |
| | LEADING TO THE EXTERIOR FBC 107.2 |
| | 4) PLEASE DETAIL COMPLIANCE WITH NEC 210.70(2)(2). FOR |
| | CONTROLLED LIGHTING OUTLET ON THE EXTERIOR OF DOORS TO |
| | PROVIDE ILLUMINATION |
| | 5) PLANS DO NOT DETAIL THE REQUIRED DIGITAL SIGNATURE |
| | OF TROY BISHOP PE. PLEASE CORRECT AS OUTLINE BELOW. |
| | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF |
| | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | DIGITALLY SEALED AND SIGNED. |
| | |
| | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS |
| | FOLLOWING PROJECTDOX INSTRUCTIONS |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |