2023-07-11 10:36:41FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE NOTES WITH THE FOLLOWING INFORMATION:
  
 A. SUPPLY BRANCH CIRCUIT SHALL BE RATED 20 AMPS AND
 DOES NOT SUPPLY OTHER CIRCUIT. NEC 600
 B. INSTALLATION OF CONDUCTORS, EQUIPMENT AND FIELD
 WIRING FOR THE ELECTRIC SIGN SHALL BE IN ACCORDANCE
 WITH NEC 600.
  
 END OF COMMENTS
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR