Plan Review Notes
Plan Review Notes For Permit 23060632
Permit Number 23060632
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-07-14 10:06:35THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) GENERATOR SPECS MUST BE SUBMITTED WITH THE PLANS.
  
 2)THERE IS A FUEL TANK INDICATED ON THE PLANS, IF THE
 FUEL TANK IS SEPARATE FROM THE GENERATOR THE SPECS FOR
 THE FUEL TANK MUST BE SUBMITTED.
  
 3)THIS BUILDING HAS A FIRE ALARM SYSTEM BUT THERE IS NO
 INDICATION OF THE GENERATOR BEING ATTACHED TO THE FIRE
 ALARM SYSTEM. PLEASE REFER TO NFPA 110 AND NFPA 72 TO
 INDICATE IF THESE WILL BE REQUIRED TO BE CONNECTED OR
 IF THE GENERATOR IS REQUIRED TO BE MONITORED PER THE
 CODES.
  
 4)IF THE GENERATOR IS REQUIRED TO BE CONNECTED AND
 MONITORED BY THE FIRE ALARM SYSTEM, SEPARATE FIRE ALARM
 DRAWINGS MUST BE SUBMITTED TO THE CITY.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR