| Plan Review Notes For Permit 23060632 |
| Permit Number |
23060632 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-14 10:06:35 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, | | | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: | | | | | | 1) GENERATOR SPECS MUST BE SUBMITTED WITH THE PLANS. | | | | | | 2)THERE IS A FUEL TANK INDICATED ON THE PLANS, IF THE | | | FUEL TANK IS SEPARATE FROM THE GENERATOR THE SPECS FOR | | | THE FUEL TANK MUST BE SUBMITTED. | | | | | | 3)THIS BUILDING HAS A FIRE ALARM SYSTEM BUT THERE IS NO | | | INDICATION OF THE GENERATOR BEING ATTACHED TO THE FIRE | | | ALARM SYSTEM. PLEASE REFER TO NFPA 110 AND NFPA 72 TO | | | INDICATE IF THESE WILL BE REQUIRED TO BE CONNECTED OR | | | IF THE GENERATOR IS REQUIRED TO BE MONITORED PER THE | | | CODES. | | | | | | 4)IF THE GENERATOR IS REQUIRED TO BE CONNECTED AND | | | MONITORED BY THE FIRE ALARM SYSTEM, SEPARATE FIRE ALARM | | | DRAWINGS MUST BE SUBMITTED TO THE CITY. | | | | | | CAITLIN L FRANCIS | | | FIRE INVESTIGATOR | | | 561-804-4728 | | | [email protected] | | | |
|