| Plan Review Notes For Permit 23060612 |
| Permit Number |
23060612 |
|
| Review Stop |
PU-CS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-05 07:33:26 | PRIOR TWO REVIEW COMMENTS WERE NOT RESOLVED. PLEASE | | | PROVIDE RESPONSE LETTER, UPDATE PLANS AS NEEDED, AND | | | CAN CONTACT WITH ANY QUESTIONS. | | | | | | -NO EXISTING DEDICATED FIRELINE WATER SERVICE ACCOUNT | | | PER UTILITY BILLING SYSTEM. AUTOFILL SHOULD BE FED BY | | | DEDICATED FIRELINE WATER SERVICE WITH DETECTOR BACKFLOW | | | ASSEMBLY. WOULD NEED TO GET THAT INSTALLED THROUGH | | | ENGINEERING DEVELOPMENT SUBMITTAL. CAN CONTACT | | | [email protected] FOR THOSE REQUIREMENTS. | | | | | | -ALSO BE AWARE THAT EXISTING DOMESTIC METERED WATER | | | SERVICE IS SUPPOSED TO BE OFF AND LOCKED FOR BACKFLOW | | | PROTECTION NONCOMPLIANCE. UTILITY EMPLOYEE VISITED SITE | | | AND COULD NOT LOCATE PROPER BACKFLOW ASSEMBLY. | | | | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|