| 2023-07-18 11:22:59 | WEST PALM BEACH DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23060579 |
| | ADD: 2603 PINEWOOD |
| | CONT: BUILTMORE CONTRACTING INC. |
| | TEL: 561-331-1476 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 18TH/23 |
| | ACTION: DENIED |
| | |
| | 1) LIFE SAFETY PLAN: |
| | 1A) BOTH THE LIFE SAFETY PLAN AND FLOOR PLAN SHOW AN |
| | ENLARGED UNISEX RESTROOM, BUT THE EXISTING WALL LINES |
| | OF THE OLD RESTROOM STILL SHOW WITH AN INSWING DOOR. |
| | THE PLUMBING FLOOR PLAN SHOWS THE WALL CONFIGURATION |
| | CORRECTLY. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | 1B) STORAGE ROOM 909 SQ. FT. SHOWS AN EMERGENCY BATTERY |
| | LIGHT WALL PACK WITH EXIT SIGN BUT THERE IS NO EXIT |
| | BENEATH THE BATTERY BACKPACK. DISCREPANCY IN PLANS. |
| | ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | 1C) NEITHER OF THE LARGE STORAGE AREAS SHOW THE EXIT |
| | DIRECTIONAL NOR THE 2 SMALL STORAGE ROOMS SHOW EXIT |
| | LIGHTS FROM THE ROOMS. 2020 FBC-BUILDING CODE SECTION |
| | 1013.1. |
| | 1D) THE TASTING ROOM SHOWS 6 CHAIRS WITH TABLE LOT THEN |
| | A 4 FOOT SECTION OF TABLE TOP, THE PLANS ARE NOT CLEAR |
| | AS TO THE HEIGHT OF EITHER SECTION OF THE TABLE, IF THE |
| | ONE WITHOUT A CHAIR IS TO REPRESENT AN ACCESSIBLE |
| | SECTION OF THE TABLE, PLANS ARE NOT CLEAR. THE LIFE |
| | SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE 2020 |
| | FBC-ACCESSIBILITY CODE. 226.1 WHERE DINING SURFACES ARE |
| | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. |
| | 1E) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 1F) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| | SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 2) THE LIFE SAFETY PLAN NOR FLOOR PLAN SHOW WALL |
| | ELEVATIONS OF THE NEW ACCESSIBLE RESTROOM AND ACCESSIB |
| | 2A) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE |
| | WATER CLOSET. SECTION 604.3 |
| | 2B) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE |
| | LAVATORIES. SECTION 606.2. |
| | 2C) TURNING SPACE DIAMETERS. SECTION 304.3 |
| | 2D) CENTERLINE OF THE WATER CLOSETS FROM THE NEAREST |
| | SIDE WALL. SECTION 604.2. |
| | 2E) HEIGHT OF THE WATERCLOSET SEATS FROM FINISH FLOOR. |
| | SECTION 604.4. |
| | 2F) HEIGHT OF THE LAVATORIES AND OR SINKS OR COUNTER |
| | SURFACES FROM THE FINISH FLOOR. SECTION 606.3. |
| | KNEE & TOE SPACE REQUIRED BY SECTION 306.2 TOE |
| | CLEARANCE, 306.3 KNEE CLEARANCES, 2020 FBC- |
| | ACCESSIBILITY CODE. INSULATE PIPES PER SECTION |
| | 2G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE BOTTOM EDGE OF THE REFLECTIVE SURFACE, MIRRORS |
| | ABOVE SINKS. SECTION 606.3. |
| | 2H) LOCATIONS, LENGTHS AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS SEE SECTION 604.5, 609.4 &. |
| | FIGURE 604. |
| | 2I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS. |
| | SECTION 604.6. |
| | 2J) CENTERLINES OF THE TOILET DISPENSER MEASURED FROM |
| | THE FRONTS OF THE WATER CLOSET. SECTION & FIGURE 604.7 |
| | 2K) 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH 602.7. |
| | 2L) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2. |
| | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT |
| | MORE THAN 80 INCHES ABOVE THE FLOOR SHALL |
| | NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE |
| | CIRCULATION PATH. |
| | 2M) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 |
| | SHALL BE PROVIDED. |
| | 2N) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| | CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| | |
| | |
| | |
| | |
| | |
| | 3) NEITHER THE LIFE SAFETY PLAN NOR THE FLOOR PLANS |
| | PROVIDE WALL FINISH SCHEDULE FOR RESTROOMS AND SERVICE |
| | SINKS. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS |
| | COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| | INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS & |
| | SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED |
| | A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 2020 FBC-BUILDING 1210.2.2 WALLS & PARTITIONS WITHIN 2 |
| | FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT |
| | OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. |
| | |
| | 4) THE SITE PLAN SHOWS AN EXTENDED STRIPPED WALKWAY TO |
| | BUILDING. THE SITE PLAN APPEARS TO BE POSSIBLY HAVE A |
| | CANOPY NOT SHOWN ON THE LIFE SAFETY PLAN NOR ANY FLOOR |
| | PLAN. WHICH DOORWAY IS GOING TO BE THE MAIN ENTRY/ EXIT |
| | DOORWAY NEEDING TO SHOW COMPLIANCE WITH 2020 |
| | FBC-ACCESS. CODE CHANGES IN LEVEL 303.2 AND 303.3. |
| | WHERE CHANGES IN LEVEL ARE PERMITTED IN THE FLOOR OR |
| | GROUND SURFACES, THEY SHALL COMPLY WITH SECTION 303. |
| | SEE 303.1 & 303.2. |
| | |
| | 5) THIS PERMIT IS FOR AN INTERIOR REMODEL, NOT EXISTING |
| | PARKING, OR ACCESSIBLE PARKING NOR EXTEND STRIPPING TO |
| | BUILDING. CLARIFICATION ONLY, NO ACTION IS REQUIRED ON |
| | THE DESIGNER???S PART. |
| | |
| | 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |