| Plan Review Notes For Permit 23060560 |
| Permit Number |
23060560 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-14 11:08:39 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEERING REQUIRES THE AWNING FABRIC TO BE | | | REMOVED WHEN WINDS ARE EXPECTED TO EXCEED 75 MPH. | | | SUBMIT TWO SETS OF DETAILED AWNING REMOVAL INSTRUCTIONS | | | WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW THIS IS DONE IN | | | TERMS THAT A LAYMAN WILL UNDERSTAND. THESE INSTRUCTIONS | | | ARE TO BE PROVIDED TO THE PROPERTY OWNER, OWNER'S | | | REPRESENTATIVE OR LESSEE. FBC 107.2.1 & FBC 3105.4 | | | | | | | | | |
|