| 2023-06-27 19:03:13 | PLAN REVIEWER: ED ROSEBERRY PX2909 | | | EMAIL: [email protected] | | | PH: 772-359-3502 | | | ***PRIMARY CONTACT IS EMAIL*** | | | | | | 1. PLEASE SUBMIT SCHEDULE AND FLOOR PLAN SKETCH SHOWING | | | LOCATION, MRH, AND WALL ZONE FOR REPLACEMENT | | | FENESTRATION. THIS IS A LISTING OF PRODUCTS DESCRIBING | | | UNIT 1, 2....ETRC. FBC 107.2 | | | 2. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT | | | FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN | | | PRESSURE TABLES HIGHLIGHTED. SGD NOT SUBMITTED AND DP | | | ARE NOT HIGHLIGHTED. FBC 107.2 | | | 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | | FBC B 1405.4. ***NOTE*** THIS IS NOT USUALLY INCLUDED | | | IN FBC/NOA. COMPLIANCE MUST BE SHOWN SEPARATELY. | | | | | | |
|