| 2023-07-14 09:55:32 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) LIFE SAFETY & ELECTRICAL SHEETS - THERE APPEARS TO |
| | BE DISCREPANCIES OF EXIT SIGNS MARKING THE TRAVEL PATHS |
| | LEADING TO AN EXIT. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN ACCORDANCE |
| | WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS 11 THROUGH |
| | 43. |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS. |
| | 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO |
| | POINT IN AN EXIT |
| | ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING |
| | DISTANCE OR 100 FT (30 M), |
| | WHICHEVER IS LESS, FROM THE NEAREST SIGN |
| | |
| | ENSURE EXIT TRAVEL PATHS IS MARKED WITH EXIT SIGNS PER |
| | NFPA 101 CH 7 ON BOTH THE LIFE SAFETY & ELECTIRCAL |
| | PLANS. |
| | |
| | 2) FIRE ALARM DOCUMENTATION - THERE DOES NOT APPEAR TO |
| | BE FIRE ALARM DOCUMENTATION IN COMPLAINCE WITH F.A.C. |
| | 61G |
| | |
| | PER F.A.C. |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER???S INTENDED USE AND |
| | PROPOSED PROTECTION OF THE BUILDING OR FACILITY AND TO |
| | PROVIDE SUFFICIENT DIRECTION TO THE INSTALLATION |
| | CONTRACTOR OR OTHER INTERESTED PARTIES REGARDING THE |
| | LAYOUT OF THE SYSTEM(S), SHALL BE INCLUDED IN THE FIRE |
| | PROTECTION SYSTEM ENGINEERING DOCUMENTS. |
| | |
| | |
| | 61G15-32.008 DESIGN OF FIRE ALARMS AND DETECTION |
| | SYSTEMS. |
| | (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE |
| | PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS, |
| | ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE |
| | SIGNALING OF EMERGENCY CONDITIONS. |
| | (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE |
| | FLORIDA BUILDING CODE (2007), THE FLORIDA FIRE |
| | PREVENTION CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY |
| | HAVING JURISDICTION. |
| | (3) FOR FIRE ALARM PLANS ON SMALL SYSTEMS BELOW THE |
| | THRESHOLD REQUIREMENTS FOR MANDATORY USE OF |
| | PROFESSIONAL ENGINEERING SERVICES, THE ENGINEER OF |
| | RECORD SHALL SPECIFY THE MINIMUM SYSTEM REQUIREMENTS. |
| | (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND |
| | DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS |
| | SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION |
| | WHEN APPLICABLE: |
| | (A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND, |
| | SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND |
| | NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. |
| | INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS |
| | DETERMINED BY THE SYSTEM???S SURVIVABILITY |
| | REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE |
| | PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS |
| | IT IS CLEAR FROM FEATURES SHOWN. |
| | (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND |
| | CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND |
| | SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS |
| | INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS, |
| | DAMPERS, AND DOORS. |
| | (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL |
| | NOTIFICATION DEVICES. |
| | (D) IDENTIFY THE CLASS AND STYLE OF CIRCUITS AS LISTED |
| | IN THE NFPA 72. |
| | (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND |
| | CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY |
| | SIGNALS BEING MONITORED OR ANNUNCIATED. |
| | (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR |
| | ADDRESSABLE, AND INDICATE ALL ZONING. |
| | (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED |
| | PROTECTIVE FEATURES. |
| | (H) LOCATE SYSTEM DEVICES THAT ARE SUBJECT TO |
| | ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR |
| | THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY |
| | OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR. |
| | (I) THE PLANS SHALL INCLUDE A SITE PLAN OF THE |
| | IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE |
| | OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE |
| | THE STRUCTURE. |
| | (J) IN BUILDINGS WERE SMOKE DETECTION WILL BE |
| | OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE |
| | ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND |
| | DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE |
| | OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A |
| | PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH |
| | AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (K) FIRE DETECTION SYSTEMS UTILIZING SMOKE DETECTION IN |
| | SITUATIONS WHERE SMOKE STRATIFICATION IS ANTICIPATED, |
| | THE DESIGN SHALL PROVIDE THE NECESSARY CRITERIA TO |
| | MITIGATE THE DETECTION PROBLEMS. |
| | (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA |
| | SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR |
| | STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING |
| | JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE |
| | FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING |
| | CODE (2007). |
| | (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO |
| | PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED |
| | EVACUATION FOR ALL HIGH-RISE BUILDINGS OR |
| | MULTI-TENANTED PROPERTIES AS DEFINED IN THE FLORIDA |
| | BUILDING CODE (2007). |
| | (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS, |
| | CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND |
| | BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE |
| | PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND |
| | INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED |
| | TO OPERATE THE SYSTEMS AS INTENDED OVER TIME. |
| | (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO |
| | SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED |
| | WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS) |
| | CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL |
| | BE COMPLETED USING THE EQUIPMENT MANUFACTURE???S DATA |
| | AND APPLICABLE NFPA 72 PROCEDURES. |
| | (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (7) WHEN THE ENGINEER DETERMINES THAT SPECIAL |
| | REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE |
| | UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE |
| | REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | |
| | EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR, |
| | THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G |
| | INFORMATION WITH THIS MASTER. |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTATION. |
| | |
| | |
| | 3) THERE IS NO INDICATION OF SMOKE CONTROL AND THE |
| | SEQUENCE OF OPERATION |
| | |
| | PER NFPA 101 |
| | |
| | 30.4 SPECIAL PROVISIONS |
| | 30.4.1 HIGH-RISE BUILDINGS. |
| | 30.4.1.1 HIGH-RISE BUILDINGS SHALL COMPLY WITH SECTION |
| | 11.8. THE PROVISIONS |
| | OF 30.3.5.3 AND 30.3.4.5 SHALL BE PERMITTED. |
| | |
| | 11.8.2.3 ALL NEW VERTICAL EXIT ENCLOSURES SERVING THE |
| | HIGH-RISE PORTION |
| | OF THE BUILDING SHALL BE SMOKEPROOF ENCLOSURES IN |
| | ACCORDANCE WITH 7.2.3 |
| | |
| | PLEASE PROVIDE THE SMOKE CONTROL AND SEQUENCE OF |
| | OPERATION PLAN |
| | |
| | 4) THERE IS AN INDICATION OF AN ELECTRIC FIRE PUMP, |
| | HOWEVER, THERE IS NO INDICATION OF THE FIRE PUMP |
| | EMERGENCY BACK UP POWER NOR ITS FUEL SUPPLY |
| | |
| | |
| | PER NFPA 101 CH 11 |
| | |
| | 11.8.5 EMERGENCY AND STANDBY POWER. |
| | 11.8.5.1 EMERGENCY POWER REQUIREMENTS FOR ELECTRIC FIRE |
| | PUMPS SHALL |
| | BE IN ACCORDANCE WITH NFPA 20. |
| | 11.8.5.2 EMERGENCY POWER REQUIREMENTS FOR DETECTION, |
| | ALARM, AND COMMUNICATIONS |
| | SYSTEMS SHALL BE IN ACCORDANCE WITH NFPA 72. |
| | 11.8.5.3 REQUIREMENTS FOR STANDBY POWER SHALL BE AS |
| | SPECIFIED IN |
| | 11.8.5.3.1 THROUGH 11.8.5.3. |
| | 11.8.5.3.1 TYPE 60, CLASS 1, LEVEL 1, STANDBY POWER IN |
| | ACCORDANCE WITH |
| | NFPA 110 SHALL BE PROVIDED. |
| | 11.8.5.3.2 THE STANDBY POWER SYSTEM SHALL HAVE A |
| | CAPACITY AND RATING |
| | SUFFICIENT TO SUPPLY ALL REQUIRED EQUIPMENT. |
| | 11.8.5.3.3 SELECTIVE LOAD PICKUP AND LOAD SHEDDING |
| | SHALL BE PERMITTED |
| | IN ACCORDANCE WITH NFPA 70. |
| | 11.8.5.3.4 THE STANDBY POWER SYSTEM SHALL BE CONNECTED |
| | TO THE |
| | FOLLOWING: |
| | (1) JOCKEY PUMP, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2 |
| | FOR SPECIALPURPOSE |
| | INDUSTRIAL OCCUPANCIES |
| | (2) AIR COMPRESSOR SERVING DRY-PIPE AND PRE-ACTION |
| | SYSTEMS, EXCEPT |
| | AS OTHERWISE PROVIDED IN 40.4.2 FOR SPECIAL-PURPOSE |
| | INDUSTRIAL |
| | OCCUPANCIES |
| | (3) EMERGENCY COMMAND CENTER EQUIPMENT AND LIGHTING |
| | (4) NOT LESS THAN ONE ELEVATOR SERVING ALL FLOORS, WITH |
| | STANDBY POWER |
| | TRANSFERABLE TO ANY ELEVATOR |
| | (5) MECHANICAL EQUIPMENT FOR SMOKEPROOF ENCLOSURES |
| | (6) MECHANICAL EQUIPMENT REQUIRED TO CONFORM WITH THE |
| | REQUIREMENTS |
| | OF SECTION 9.3 |
| | (7) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PER NFPA |
| | |
| | NFPA 101 CHAPTER 7 SECTION 7.9 |
| | |
| | 7.9.1 FUEL TANKS SHALL BE SIZED TO ACCOMMODATE THE |
| | SPECIFIC |
| | |
| | EPS CLASS. |
| | |
| | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| | AND MAINTAINED |
| | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| | 54, NATIONAL |
| | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| | CODE. |
| | |
| | |
| | PLEASE PROVIDE DETAILS AND CONFIRMATION OF THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 4) THE ADDRESSING ON THE PLANS AND ON THE APPLICATION |
| | DO NOT MATCH. APPLICATION LISTS 4708 N FLAGLER AS THE |
| | PROJECT ADDRESS AND THE PLANS INDICATE THE ADDRESS |
| | BEING 4714 N FLAGLER. |
| | |
| | PLEASE REVIEW AND FOR THE OFFICIAL RECORD, CORRECT AS |
| | APPLICABLE |
| | |
| | |
| | |
| | 5) THERE IS AN INDICATION OF A EMERGENCY COMMAND |
| | CENTER. |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE |
| | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL |
| | BE APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER |
| | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 |
| | HOUR. |
| | |
| | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A |
| | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF |
| | 10 FT (3050 MM). |
| | |
| | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS |
| | (4) WORK TABLE. |
| | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY |
| | COMMAND CENTER. |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION |
| | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |
| | NFPA 101 |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | PLEASE ENSURE COMPLIANCE WITH THE REQUIREMENTS. |
| | |
| | |
| | |
| | 6) THERE ARE NO INDICATIONS OF COMPLIANCE WITH THE |
| | REQUIRMENTS OF EMERGENCY RADIO COMMUNICATIONS |
| | |
| | TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| | SYSTEMS. |
| | 24.9.1 GENERAL. |
| | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| | CAPABLE |
| | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| | FREQUENCIES |
| | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| | INSTALLED |
| | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| | AUTHORITY |
| | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| | DEGRADE |
| | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED |
| | FOR |
| | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| | SUCCESSFUL |
| | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| | FOR THE |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| | BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH |
| | FIRE DEPARTMENT. |
| | |
| | TESTING SHALL BE BY AN ACCEPTABLE NATIONAL STANDARD |
| | DOCUMENTING PERCENTAGES NOTED ABOVE AND BY ACTUAL RADIO |
| | TESTING BY FIRE PERSONNEL. |
| | |
| | IF THE MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL |
| | AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM |
| | 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | CONTACT SHALL BE MADE TO KEN DECKER, PALM BEACH COUNTY |
| | PUBLIC SAFETY RADIO SYSTEMS MANAGER, |
| | [email protected], 561-233-0837; AS OUR RADIOS OPERATE |
| | ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | NO PERMIT SHALL BE SUBMITTED OR BDA SYSTEM INSTALLED |
| | UNTIL ALL DOCUMENTATION IS REVIEWED BY PBC & THE OFFICE |
| | OF THE FIRE MARSHAL AND SUBSEQUENTLY APPROVED FOR |
| | INSTALL OR PARTIAL INSTALL. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |